APPLICABILITY & EFFECTIVITY  
Effective for all systems manufactured after May 1, 2001  
Instruction Manual Part Number FS-8700-52  
5/22/2002  
FS-8700-52 Notifier AM6000  
Driver Manual  
1. Notifier AM6000 Description  
The Notifier AM6000 driver is a seial driver. It allows the FieldServer to transfer data from a Notifier  
AM6000 panel over either RS232 or RS485 using Notifier AM6000 protocol. There are eight RS232 and  
two RS485 ports standard on the FieldServer. The FieldServer can only a passive Client.  
The driver receives messages intended for a system printer, interprets these messages by filling in data  
arrays in the FieldServer. This data is available for other devices or PLC's to read.  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 1  
FS-8700-52 Notifier AM6000  
Driver Manual  
2. Driver Scope of Supply  
2.1 Supplied by FieldServer for this driver  
FieldServer  
Technologies  
PART #  
DESCRIPTION  
8915-10  
UTP cable (7 foot) for RS232 use  
UTP cable (7 foot) for Ethernet connection  
RJ45 to DB9F Connector adapter  
RJ45 to DB25M connection adapter  
RS485 connection adapter  
8917-02  
8917-01  
SPA59132  
Driver Manual.  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 2  
FS-8700-52 Notifier AM6000  
Driver Manual  
3. Hardware Connections  
Configure the Notifier AM6000 according to manufacturer’s instructions.  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 3  
FS-8700-52 Notifier AM6000  
Driver Manual  
4. Configuring the FieldServer as a Notifier AM6000 Client  
For a detailed discussion on FieldServer configuration, please refer to the instruction manual for the  
FieldServer. The information that follows describes how to expand upon the factory defaults provided in  
the configuration files included with the FieldServer (See “.csv” files on the driver diskette).  
This section documents and describes the parameters necessary for configuring the FieldServer to  
communicate with a Notifier AM6000 Server.  
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order  
to enable the FieldServer for Notifier AM6000 communications, the driver independent FieldServer  
buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be  
declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in  
the “Client Side Map Descriptors” section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.  
4.1 Data Arrays  
Section Title  
Data_Arrays  
Column Title  
Data_Array_Name  
Data_Format  
Function  
Legal Values  
Provide name for Data Array  
Provide data format. Each data array  
can only take on one format.  
Up to 15 alphanumeric characters  
FLOAT, BIT, UInt16, SInt16,  
Packed_Bit, Byte, Packed_Byte,  
Swapped_Byte  
Data_Array_Length  
Number of Data Objects. Must be larger 1-10,000  
than the data storage area required for  
the data being placed in this array.  
Example  
//  
Data Arrays  
//  
Data_Arrays  
Data_Array_Name,  
DA_AI_01,  
DA_AO_01,  
DA_DI_01,  
DA_DO_01,  
Data_Format,  
UInt16,  
UInt16,  
Bit,  
Data_Array_Length  
200  
200  
200  
200  
Bit,  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 4  
FS-8700-52 Notifier AM6000  
4.2 Client Side Connections  
Driver Manual  
Section Title  
Connections  
Column Title  
Function  
Legal Values  
P1-P8, R1-R2  
Port  
Specify which port the device is  
connected to the FieldServer  
Specify baud rate  
Baud*  
2400 (Only baud rate supported by  
the Notifier port)  
Parity*  
Data_Bits*  
Specify parity  
Specify data bits  
Even  
7
Stop_Bits*  
Protocol  
Specify stop bits  
1
Specify protocol used  
AM6000  
Handshaking*  
Poll Delay*  
Specify hardware handshaking  
Time between internal polls  
None  
0-32000 seconds  
default 1 second  
Example  
// Client Side Connections  
Connections  
Port, Baud, Parity, Protocol, Data_bits, Handshaking, Poll_Delay  
P8, 2400, Even, AM6000, 7,  
None,  
0.100s  
4.3 Client Side Nodes  
Section Title  
Nodes  
Column Title  
Node_Name  
Function  
Provide name for node  
Legal Values  
Up to 32 alphanumeric characters  
Node_ID  
Modbus station address of physical 1-255  
server node  
Protocol  
Port  
Specify protocol used  
Specify which port the device is  
connected to the FieldServer  
Modbus_RTU, Modbus/TCP, etc.  
P1-P8, R1-R2  
Example  
// Client Side Nodes  
Nodes  
Node_Name, Protocol, Port  
Panel1, AM6000,  
P8  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 5  
FS-8700-52 Notifier AM6000  
Driver Manual  
4.4 Client Side Map Descriptors  
4.4.1 FieldSe rver Specific Map Descriptor Parameters  
Column Title  
Map_Descriptor_Name  
Data_Array_Name  
Function  
Name of this Map Descriptor  
Name of Data Array where data is One of the Data Array names from  
Legal Values  
Up to 32 alphanumeric characters  
to be stored in the FieldServer  
Starting location in Data Array  
“Data Array” section above  
0 to maximum specified in “Data  
Array” section above  
Data_Array_Location  
Function  
Function of Client Map Descriptor Passive  
4.4.2 Driver Specific Map Descriptor Parameters  
Column Title Function  
Legal Values  
Node_Name  
Name of Node to fetch data from  
One of the node names  
specified in “Client  
Node Descriptor” above  
Data_Type  
Length  
Data type  
Register, Coil, AI, DI  
Length of Map Descriptor. This value is important  
when a 'Block Ack' message is received as it tells  
the driver how much of the data array to zeroise.  
Loop/Device Address  
1 - 1000  
501, 302  
Address  
In the format mmnn where mm is the loop number  
and nn is the device number. Together they forma a  
composite device number.  
AM6000 Driver  
specific parameters &  
keywords.  
Am6000_typeID  
Used to differentiate between device and system  
type messages.  
Device-only,  
System_trbl,  
device&type.  
system-Styl2,  
catch-all  
Additional notes are  
provided in section 5.1  
Am6000_Status  
Allows direction of alarm or trouble states to  
different data arrays.  
Any, Alarm, trouble,  
erase, on , eraseon  
Additional notes are  
provided in section 5.2  
Additional notes are  
provided in section 5.3  
AM6000_Ackable  
Tells the driver that the data area of this mapdesc  
must be Zeroised when a block ack is received.  
Provided for debugging and test purposes only.  
Tells the driver which debug message to send. This  
parameter is for use by FieldServer Technologies  
only.  
Am6000_simulation  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 6  
FS-8700-52 Notifier AM6000  
4.4.3 Timing Parameters  
Driver Manual  
Legal Values  
Column Title  
Function  
Scan_Interval  
Rate at which data is polled  
>0.1s  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 7  
FS-8700-52 Notifier AM6000  
Driver Manual  
4.4.4 Map Descriptor Example.  
Name of the data  
array that will be  
updated when this  
map descriptor is  
used.  
The position in the data  
The range of  
array that corresponds to  
device whose number is  
equal to the Address  
Parameter.  
device address is  
determined by this  
parameter.  
Because address is  
500 and length is  
100 in this  
example all  
devices 500 to 599  
will be  
All map  
descriptors for the  
AM6000 Notifier  
driver must be  
passive.  
In this example device  
500's state will be strored  
in the 0th element of the  
data array called  
DEVICE_STATES_LOOP1  
Map_block_Name, scan_interval, Data_Array_Name,  
DEVICES_100_199, 1.0s, DEVICE_STATES_LOOP1, 0,  
Data_Array_Offset, Function, node_name, AM6000_TypeID, Address , Length , am6000_Ackable  
passive, node_a, device-only, 500 100 , Yes  
,
Connects this  
map descriptor  
to a node  
whose name is  
'node_a' and  
thus connects  
the map  
When a Block  
The device address of the first  
Acknowledge or System  
Reset message is received  
the driver will set the  
portion of the data array  
DEVICE_STATES_LOO  
P1 starting at  
Data_Array_Offset for  
Length number of  
elements to zero.  
This keyword indicates that  
device to be processed by this map  
descriptor. Devices are allocated to  
loops. The device address consists  
of a mmnn format where mm is the  
loop number and nn is the device  
number.  
this map descriptor will only  
be used to process device  
state messages. This makes  
the address and length  
parameters very important.  
descriptor to a  
port.  
In this example the address is set to  
500 this indicated that the first  
device to be processed by this map  
desc. Is on loop 5 and is device  
zero.  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 8  
FS-8700-52 Notifier AM6000  
Driver Manual  
Name of the data  
array that will be  
updated when this  
map descriptor is  
used.  
When a Block  
Acknowledge or System  
Reset message is  
received the driver will  
set the portion of the  
data array  
All map  
descriptors for the  
AM6000 Notifier  
driver must be  
passive.  
DEVICE_STATES_LO  
OP1 starting at  
Data_Array_Offset for  
Length number of  
elements to zero.  
Map_block_Name,scan_interval, Data_Array_Name,  
Data_Array_Offset, Function, node_name, AM6000_TypeID, Length , am6000_Ackabl  
MD1,  
1.0s,  
SYSTEM_TROUBLES2, 5,  
passive, node_a,  
system-styl2,  
50  
,
Yes  
System Trouble Messages are  
processed using this map  
descriptor. Only one map  
descriptor like this is necessary for  
a whole system.  
This indicates Style2 is being used.  
Thus when system trouble message  
number n is processed the nth  
element of data array starting at  
location 5 (this example) will be  
set to 1.  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 9  
FS-8700-52 Notifier AM6000  
5. Driver Notes  
Driver Manual  
5.1 Map Descriptor Keywords  
5.1.1 AM6000_TypeID  
This keyword sets up a category of messages. If you are interested in device state's use the  
keyword device-only. If you are interested in system trouble messages use the keyword system-  
trbl (An alternate method for reporting system trouble messages is provided using the keyword  
system-styl2. )  
device-only  
Only device based messages are processed using map descriptors with this keyword. The Address  
and Length parameters define the range of devices processed using the map descriptor. A device  
address consists of a loop and device number. This driver treats the two parts as a single device  
address. Thus loop 5 device 2 becomes address 502 for this driver and a map descriptor with an  
address of 500 and a length of 100 would process a message from device 2 on loop 5.  
system-trbl  
System Trouble messages are processed a numeric value is stored in the first element of the map  
descriptor's data array. If a new system trouble message is processed then the value is overwritten  
with the new value.  
system-styl2  
This is an alternate style for processing System Trouble messages. If system trouble message  
whose index in the list below is n is received then the nth element of the data array is set to one.  
Make sure the length parameter is set to at least 50.  
Catch-all  
The use of this keyword is described in section 5.2  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 10  
FS-8700-52 Notifier AM6000  
5.1.2 AM6000_Status  
Driver Manual  
Device state messages report a number of different states for the device. These states are refered  
to as the device status.  
The following are possible values of this parameter. Any, alarm, trouble, on, erase, eraseon.  
If you do not use this parameter in a device-only map descriptor then the driver uses the default  
value of Any. This means that any device state message will result in the same data array being  
updated. Thus a trouble/on/alarm message will result in the array being set to a 1.  
If you want to maintain separate array's for each state the you use this parameter. For one device  
address range you would have multiple map descriptors, each with a different AM6000_Status  
keyword.  
You should note that the keyword, erase, results in the data array value being set to zero when a  
message reports the device state as 'ERASE'. The keyword eraseon sets the value to one, when  
the same message is received.  
5.1.3 AM6000_Ackable  
This parameter tells the driver that the data array portion associated with this map descriptor can  
be set to zero when a Block Acknowledge or System Reset message is received.  
You set this parameter to one of the following legal keywords: yes, no.  
The Data_Array_Location and Length parameters are used to determine what portion of the  
associated data array must be set to zero.  
5.1.4 AM6000_Simulation  
This keyword is for used by FieldServer Technologies Engineers and is used for testing this  
driver.  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 11  
FS-8700-52 Notifier AM6000  
5.2 Statistics  
Driver Manual  
This driver does not keep statistics for each map descriptor. Statistics are maintained for the  
connection to the Am6000 Notifier device.  
Count of received messages  
and bytes. A complete  
received message is 82 bytes  
long and thus if all messages  
are received correctly the  
byte count should be a  
multiple of 82.  
This indicates the number of  
times a 'Block Ack' or  
'System Reset' message have  
been applied.  
If you have 5 'Ackable' map  
descriptors and one 'Block  
Ack' message was received a  
count of 5 would be  
reported. (One message  
applied 5 times).  
You will need to count the  
number of 'ackable' map  
descriptors to use this  
statistic meaningfully.  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 12  
FS-8700-52 Notifier AM6000  
Driver Manual  
This statistic indicates the number of messages that  
were received but were ignored by the driver.  
Messages are ignored for one of two reasons. Firstly,  
the driver might not understand the message and  
secondly because the driver doesn't know what to do  
with the data from the message.  
Ignored Messages  
Ignored messages are very important since they do not result in the data arrays being updated.  
Messages are ignored for one of two reasons.  
Firstly, the driver might not understand the message and secondly because the driver doesn't  
know what to do with the data from the message. The message t may contain a keyword or be  
formatted in a way that cannot be understood.. It may be the case that the equipment  
manufacturer adds new features to the protocol. FieldServer Technologies needs to be informed  
of any such messages so that this driver can be updated.  
Secondly, you may have omitted to define a map descriptor which tells the driver what to do with  
the data from an incoming message. For example, say a map descriptor is defined for address 501  
with a length of 50 but a message is received from device 575. Clearly the map descriptor's  
device address range does not extend ass far as 575 and thus the driver doesn't know where to  
store device 575's data.  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 13  
FS-8700-52 Notifier AM6000  
Catching Ignored Messages  
Driver Manual  
To assist you catch and monitor ignored messages the driver provides a special map descriptor  
keyword.  
Make a map descriptor and set the parameter AM6000_TypeID 's value to Catch-All. Make sure  
that this is the last map descriptor in the csv file. The map descriptor requires a data length of at  
least 82 and when using RUI_Debug you should view the data array in <S>tring mode.  
The driver will place any ignored messages in this buffer. You will be able to read the message in  
<S>tring mode an make a decision on the necessary corrective action. If there are multiple  
messages being ignored the buffer will be overwritten.  
You could use your PLC / control device / Scada to monitor the first byte of this data array and  
generate an alarm if the value is non-zero. Thus, even though a message has been ignored you  
system will know about it.  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 14  
FS-8700-52 Notifier AM6000  
Driver Manual  
5.3 Listing of System Trouble Messages  
Msg Index Message  
0 !!! ILLEGAL !!!  
1 MAINS TROUBLE  
2 POWER LOW ON MAIN SUPPLY  
3 POWER LOW ON AUXILIARY SUPPLY  
4 POWER LOW ON BATTERY-CHARGER  
5 POWER OVERVOLTAGE ON MAIN SUPPLY  
6 POWER OVERVOLTAGE ON BATTERY-CHARGER  
7 FAILURE OR OVERLOAD ON MAIN SUPPLY  
8 FAILURE OR OVERLOAD ON AUXIL. SUPPLY  
9 FAILURE ON BATTERY-CHARGER  
10 DISCONNEC. BATT. OR FUSE FAILURE  
11 BATTERY EXHAUSTED  
12 BATTERY CHARGER UNBALANCED  
13 AUX. SUPPLY DISCONNECTED  
14 AUX. SUPPLY USER FUSE  
15 MAIN SUPPLY USER FUSE  
16 SIREN FUSE  
17 EARTH TROUBLE  
18 SIREN SUPERV.LINE INTERRUPTED  
19 BATTERY FAILURE  
20 WIRE CUT ON LINE  
21 SHORT CIRCUIT ON LINE  
22 PRINTER: OFF LINE/BUFFER FULL/PAPER END  
23 COMMUNICATION ERROR ON  
24 LOW VOLTAGE ON LINE  
25 SIDE A OPEN ON LINE  
26 SIDE B OPEN ON LINE  
27 SYSTEM KEYPAD TROUBLE  
28 INTERNAL PROGR.ENABLING JUMPER :ENABLED  
29 SYSTEM START UP  
30 CPU RESET OR WATCH-DOG FAILURE  
31 CRT-TERMINAL : OFF-LINE  
32 FLASH MEMORY ERROR ON  
33 SIREN SUPERV.LINE  
34 LINE  
35 ANNUNC.  
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042  
Page 15  

LaCie 34 User Manual
Kenwood KDC 2094 User Manual
Hamilton Beach 47214 User Manual
Fujitsu MHS2040AT User Manual
Fellowes 220 2 User Manual
Esoteric X 03 User Manual
Emerson CKS1855 User Manual
Coleman 5008 User Manual
Alpine CDA 9833 User Manual
Addonics Technologies Computer Drive RT134SDEU3 User Manual