FieldServer FS 8700 22 X30 User Manual

A Sierra Monitor Company  
Driver Manual  
(Supplement to the FieldServer Instruction Manual)  
FS-8700-22 X30 DeviceNet Slave Adapter  
Driver  
APPLICABILITY & EFFECTIVITY  
Effective for all systems manufactured after May 1, 2001  
Driver Version:  
1.00  
Document Revision: 2  
FS-8700-22_X30_DeviceNet_Slave Manual  
Page 3 of 12  
1.  
X30 DeviceNet Slave Description  
The X30 DeviceNet Slave Adapter driver can be used to emulate a single slave station on a  
DeviceNet network. The FieldServer DeviceNet adapter is implemented as an ODVA profile 12  
communications adapter and acts as a group 2 only server on the DeviceNet network.  
Standard DeviceNet baudrates of 125k, 250k and 500kbit/s are supported. DeviceNet  
masters/scanners can open an IO connection of up to 512 Bytes in each direction to the  
FieldServer.  
Max Nodes Supported  
FieldServer Mode Nodes Comments  
Server  
1
The FieldServer can only emulate one DeviceNet Slave station  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-22_X30_DeviceNet_Slave Manual  
Page 4 of 12  
2.  
Driver Scope of Supply  
2.1. Supplied by FieldServer Technologies for this driver  
FieldServer Technologies  
PART #  
Description  
FS-8700-22  
Driver Manual.  
X30-DeviceNet-Slave  
Anybus-S DeviceNet Card  
2.2.  
2.2.1.  
Provided by the Supplier of 3rd Party Equipment  
Required 3rd Party Software  
RSNetWorx, RSLogix or another Network Scheduling Tool.  
2.2.2.  
Connection to a properly terminated DeviceNet network.  
Required 3rd Party Configuration  
2.2.3.  
Optional Items  
PART # Vendor/Manufacturer  
Description  
-
HMS-Networks  
Anybus-S DeviceNet eds file  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-22_X30_DeviceNet_Slave Manual  
Page 5 of 12  
3.  
Hardware Connections  
The FieldServer is connected to the DeviceNet network as shown in the connection drawing  
below.  
3.1.  
Hardware Connection Tips / Hints  
Use the recommended network cable and terminators as specified by the DeviceNet  
network organization and/or the manufacturer of your network equipment.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-22_X30_DeviceNet_Slave Manual  
Page 6 of 12  
4.  
Configuring the FieldServer as a DeviceNet Slave  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
Configuration Manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” files  
provided with the FieldServer).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with a DeviceNet Master/Scanner.  
The configuration file tells the FieldServer about its interfaces, and the routing of data required.  
In order to enable the FieldServer for DeviceNet communications, the driver independent  
FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual  
node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to  
the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to  
do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
4.1.  
DeviceNet Settings  
Section Title  
FieldServer  
Column Title  
Function  
Legal Values  
System_Station_Address*  
DeviceNet MAC ID of the FieldServer  
0-63  
Note:  
The DeviceNet MAC ID can also be set via the DIP switches on the side of the FieldServer  
but then the system station address parameter must be removed from the configuration file.  
Refer to Appendix B.1 for more information.  
Example  
// FieldServer  
FieldServer  
Title,  
DeviceNet_Test,  
System_Station_Address  
5
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-22_X30_DeviceNet_Slave Manual  
Page 7 of 12  
4.2.  
Server Side Connection Descriptors  
Section Title  
Connections  
Column Title  
Adapter  
Protocol  
Function  
Adapter Name  
Protocol name  
Legal Values  
DNet  
X30_DNet_Slave  
DNet_Slave_Baudrate Baudrate  
125K , 250K , 500K  
Example  
// Server Side Connections  
Connections  
Adapter,  
DNet,  
Protocol,  
X30_DNet_Slave,  
DNet_Slave_Baudrate  
500K  
4.3.  
Server Side Node Descriptors  
Section Title  
Nodes  
Column Title  
Node_Name  
Node_Id  
Function  
Provide name for node  
MACID  
Legal Values  
Up to 32 alphanumeric characters  
0 - 63 (same as system_station_address)  
X30_DNet_Slave  
Protocol  
Specify protocol used  
Example  
// Server Side Nodes  
Nodes  
Node_Name,  
DN5,  
Node_Id,  
01,  
Protocol  
X30_DNet_Slave  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-22_X30_DeviceNet_Slave Manual  
Page 8 of 12  
4.4.  
4.4.1.  
Server Side Map Descriptors  
FieldServer Specific Map Descriptor Parameters  
Column Title Function Legal Values  
Map_Descriptor_Name Name of this Map Descriptor  
Up to 32 alphanumeric  
characters  
Name of Data Array where One of the Data Array names  
data is to be stored in the from “Data Array” section  
Data_Array_Name  
Data_Array_Offset  
FieldServer  
above  
Starting location in Data 0 to maximum specified in  
Array  
“Data Array” section above  
RDBC -Reads data from the  
Function of Server Map local input buffer  
Function  
Descriptor  
WRBC -Writes data to the  
local output buffer  
Scan_Interval  
Buffers Update Period  
> 0.001s  
4.4.2.  
Driver Specific Map Descriptor Parameters  
Column Title Function Legal Values  
One of the node names  
specified in “Server Node  
Descriptor” above  
Node_Name  
Name of Node  
BYTE, WORD, DWORD,  
FLOAT, BOOL  
RDBC: 0 – 511  
DeviceNet_Data_Type  
Address  
Data Type of local buffer  
Byte offset into local buffer  
WRBC: 0 – 511  
BYTE: 1 – 512  
Number  
DeviceNet_Data_Type  
items in local buffer  
of WORD: 1 – 256  
DWORD: 1 – 128  
Length  
FLOAT: 1 –128  
BOOL: 1 – 4096  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-22_X30_DeviceNet_Slave Manual  
Page 10 of 12  
Appendix A. Advanced Topics  
Appendix A.1. DeviceNet X30 LED indicators  
LED 1 – Reserved  
LED 2 – Network Status  
Color  
Frequency  
Off  
Description  
Not powered / Not online  
-
Green  
Green  
Red  
On  
Flashing  
On  
Link OK, online, connected  
Online, not connected  
Critical link failure  
Red  
Flashing  
Connection timeout  
LED 3 – Module Status  
Color Frequency  
Description  
-
Off  
Not powered  
Green  
Green  
Red  
On  
Flashing  
On  
Device operational  
Data size bigger than configured  
Unrecoverable fault  
Minor fault  
Red  
Flashing  
LED 4 – Reserved  
Appendix A.2. Using RSNetWorx  
APPLICATION NOTE: Establishing I/O communication between AnyBus-S DeviceNet  
using RsNetWorx for DeviceNet  
Appendix A.3. Using RSLogix 5000  
APPLICATION NOTE: Reading/writing data from AnyBus-S DeviceNet using  
ControlLogix5000 MSG instruction  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-22_X30_DeviceNet_Slave Manual  
Appendix B. Driver Notes  
Page 11 of 12  
Appendix B.1. Setting the FieldServer’s DeviceNet MAC ID and Baudrate  
The MAC ID and Baudrate can be set in the FieldServer’s CSV file using the  
System_Station_Address and DNet_Slave_Baudrate parameters or it can be set with the  
DIP switches. Note that the System_Station_Address parameter must be removed from the  
config file if the DIP switch settings is to be used.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-22_X30_DeviceNet_Slave Manual  
Page 12 of 12  
THIS PAGE INTENTIONALLY LEFT BLANK  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  

Multi Tech Systems Computer Accessories ISI4608 PCI User Manual
Mr Coffee PRX23 User Manual
Motorola r750plus User Manual
LG Electronics LG Lifes Good Cell Phone MFL67874301 User Manual
Kenwood KDC 122S User Manual
Kambrook Computer Drive KEB413 User Manual
JVC KD G311 User Manual
Huawei Technologies Cell Phone C8800 User Manual
Curtis KCR2613 User Manual
Black Box LTD8B User Manual