Contents
Quick Start Guide ..........................................................................................................................4
Standard Accessories...................................................................................................................5
Additional Required Items ............................................................................................................5
Equipment Overview.....................................................................................................................5
Safety Precautions ........................................................................................................................6
Installing the Power Input Retention Bracket ............................................................................6
Mounting .........................................................................................................................................7
Connecting to the Power Source.................................................................................................7
Connecting Devices ......................................................................................................................8
Connecting the Sensors ...............................................................................................................8
Connecting to the Unit (Remote Monitoring Units Only)..........................................................8
Interfaces ......................................................................................................................................10
HTML Interface ............................................................................................................................11
Command Line Interface ............................................................................................................18
SSL................................................................................................................................................34
SSH ...............................................................................................................................................35
SNMP............................................................................................................................................36
Resetting to Factory Defaults ....................................................................................................46
Uploading Firmware....................................................................................................................46
Technical Specifications.............................................................................................................47
1. Getting Started
Quick Start Guide
The following instructions will help you quickly install and configure your AmpMeter PDU for use on your
network. For detailed information on each step, go to the page number listed to the right.
For your network security, MGE UPS SYSTEMS strongly recommends the removal of the predefined
user account prior to attachment to your network.
1. Mount the AmpMeter PDU..................................................................................................................... 6
2. Connect to the power source................................................................................................................. 3
3. Connect the devices to the AmpMeter PDU.......................................................................................... 7
4. Connect to the AmpMeter PDU ............................................................................................................. 8
5. Configure the AmpMeter PDU (remote monitoring units only) .............................................................. 8
•
•
•
•
Login as the predefined Administrator (MGEUPS/MGEUPS) ..................................................... 10
Create new administrative user account ............................................................................... 14, 22
Configure location and tower names..................................................................................... 12, 26
Remove the predefined Administrator................................................................................... 14, 22
6. Connect the AmpMeter PDU to the network
Page 4 - 301-0399-3 Rev B.
2. Installation
Before installation, refer to the following lists to ensure that you have all the items shipped with the unit as well
as all other required items.
Standard Accessories
•
Mounting hardware - two removable flanges with four M4 screws and two mounting L-brackets with nut
plates and four sets of screws and washers.
For remote monitoring units only:
•
•
RJ45 to RJ45 crossover cable
RJ45 to DB9F serial port adapter (for connection to standard DB9M DTE serial port)
Additional Required Items
•
•
Phillip screwdriver
Screws, washers and nuts to attach the unit to your rack
Equipment Overview
•
•
•
•
•
The Input Current LED(s) displays the current load for each infeed or electrical phase per infeed.
Each Branch Circuit / electrical phase is color-coded for easy identification.
The power inlet/cord(s) connects the PDU to the electrical power source.
Two RJ45 connectors for Serial (RS-232) and Ethernet connection (remote monitoring units only).
Two mini RJ11 connectors for Temperature/Humidity sensors (remote monitoring units only).
I
n
p
u
t
C
u
rr
e
n
t
1 Power Input
2
2 Input Current LED
3 Ethernet / RS232 Ports
4 Temperature / Humidity Ports
t
c
B
r
e
n
a
n
c
n
o
h
c
1
is
ly
d
p
s
p
y
u
a
s
r
g
lw
e
w
e
n
i
A
n
o
e
s
p
p
.
k
e
o
l
a
c
h
t
r
o
h
o
f
e
b
c
ri
d
r
t
c
o
c
e
l
e
)
id
1
o
v
a
h
c
n
o
t
a
r
L
E
D
1
B
(
F
1
1
F
s
c
o
h
c
z
e
s
e
h
c
l
r
e
n
it
a
r
v
b
é
é
'
e
u
d
d
iq
in
,
tr
f
s
c
A
e
e
l
u
é
iq
.
r
r
t
i
r
v
c
le
t
n
)
le
b
u
é
a
c
'o
2
d
le
h
c
n
a
v
a
a
r
B
(
L
E
2
F
2
F
2
g
n
u
it
le
z
t
r
e
o
v
N
r
e
l
n
e
m
p
m
u
m
p
I
u
k
n
s
e
u
h
c
g
a
a
a
l
m
h
c
f
u
S
A
n
n
e
.
e
h
n
d
c
e
s
i
i
d
tr
e
k
m
r
e
l
e
e
v
M
G
u
z
N
E
U
O
e
I
f
P
S
S
T
e
Y
S
T
U
e
E
M
A
ir
S
t
C
n
e
w
v
s
i
z
w
r
w
p
e
.
m
o
T
m
g
a
e
s
l
y
S
u
p
n
m
s
th
o
.
c
i
a
o
w
e
s
m
r
t
e
u
f
C
c
a
D
l
e
p
p
U
e
y
t
r
d
n
a
3
I
I
I
4
S
2
e
n
s
o
r
1
A
1
2
3
1
2
B
r
a
n
c
h
2
1
3
2
3
M
U
G
E
P
S
S
Y
S
T
E
2
M
S
w
w
w
.m
g
e
A
u
p
m
s
.c
p
1
o
M
m
e
t
e
1
r
P
D
U
B
2
1
1
Figure 0.1 AmpMeter PDU Views
301-0399-3 Rev B. - Page 5
2. Installation
Safety Precautions
This section contains important safety and regulatory information that should be reviewed before installation
Only for installation and use in a
Restricted Access Location in
accordance with the following
installation and use instructions.
Seulement pour l’installation et
l’utilisation dans une Zone Interdite
conformément aux installations et
l’utilisation des indications suivants.
Nur zur Installation und Verwendung in
einem Sicherheitsbereich gemäß den
folgenden Installations- und
Verwendungsanleitungen.
This equipment is designed to be
installed on a dedicated circuit.
Cet équipement est conçu à être
installé sur un circuit spécialisé.
Diese Ausrüstung ist zur Installation in
einem festen Stromkreis vorgesehen.
Dedicated branch circuit must have
circuit breaker or fuse protection; 3-
phase/multi-pole dedicated branch
circuits must have circuit breaker or fuse
protection for each phase/pole located
together. PDUs have been designed
without a master circuit breaker or fuse
to avoid becoming a single point of
failure. It is the customer’s responsibility
to provide adequate protection for the
dedicated branch power circuit.
Le circuit de dérivation spécialisé doit Der als Standleitung verwendete
être équipé de disjoncteurs ou de
fusibles ;
Lorsqu'ils sont triphasés ou
Zweigstromkreis muss mit einem
Überlastschalter bzw. einer Sicherung
ausgestattet sein; bei Standleitungs-
multipolaires, ils doivent être équipés Zweigstromkreisen mit 3
de disjoncteurs ou de fusibles sur
chaque phase ou pôle. Les PDU ont
Phasen/mehreren Polen müssen
zusammengehörige Phasen/Pole
été conçus sans disjoncteur ou fusible individuell durch einen Überlastschalter
principal afin de ne pas constituer le
seul point de rupture. Le client est
bzw. eine Sicherung geschützt sein. In
PDUs ist kein Haupt-Überlastschalter
seul responsable de la protection des bzw. keine Hauptsicherung installiert.
Protection should not exceed the Total
Input Rating of the PDU and must meet
all applicable local, state and federal
codes and regulations.
circuits électriques de dérivation
spécialisés. Cette protection ne doit
pas excéder la consommation totale
en entrée du PDU et doit être
conforme aux normes et à la
réglementation locales, d'état et
fédérales.
Dadurch wird ausgeschlossen, dass die
PDU als alleinige Schwachstelle in
Frage kommt. Es liegt in der
Verantwortung des Kunden, den als
Standleitung verwendeten
Zweigstromkreis durch entsprechende
Schutzmaßnahmen vor Überlastung zu
schützen. Der Wert für den
Überlastschutz darf nicht über dem Wert
für die Eingangsstromstärke der PDU
liegen und muss geltenden örtlichen und
staatlichen Bestimmungen entsprechen.
The plug on the power supply cord shall
be installed near the equipment and
shall be easily accessible.
La prise sur le cordon d’alimentation
Der Stecker des Netzkabels muss in der
sera installée près de l’équipement et Nähe der Ausrüstung installiert werden
sera facilement disponible.
und leicht zugänglich sein.
Always disconnect the power supply
cord before opening to avoid electrical
shock.
Toujours déconnecter le cordon
d’alimentation avant d’ouvrir pour
éviter un choque électrique.
Ziehen Sie vor dem Öffnen immer das
Netzkabel heraus, um die Gefahr eines
elektrischen Schlags zu vermeiden.
WARNING! High leakage current!
Earth connection is essential before
connecting supply!
ATTENTION ! Haut fuite très
ACHTUNG! Hoher Ableitstrom! Ein
possible ! Une connection de masse Erdungsanschluss ist vor dem
est essentielle avant de connecter
l’alimentation !
Einschalten der Stromzufuhr
erforderlich!
Installing the Power Input Retention Bracket
For Switched PDUs with a total maximum output <30A, it may be
necessary to install the power input retention bracket prior to mounting
the Switched PDU within the rack.
To install the power input retention bracket:
1. Remove the two screws attaching the IEC 60320 C19 inlet to the
enclosure.
2. Assemble and attach the retention bracket to the enclosure as
shown.
Figure 2. Retention Bracket assembly
Page 6 - 301-0399-3 Rev B.
2. Installation
Mounting
Figure 3. Mounting
Horizontal/Rack
Vertical/Tower
1. Select the appropriate bracket mounting points
for proper mounting depth within the rack.
2. Attach the brackets to these mounting points
with two screws for each bracket.
3. Install the enclosure into your rack, using the
slots in each bracket. The slots allow about ¼
inch of horizontal adaptability to align with the
mounting holes of your rack.
1. Attach the removable flanges to the mount
points on the rear of the enclosure using M4
screws.
2. Attach the mounting L-brackets to the flanges
with the supplied screws, washers and nut
plates. The slots allow about 1½ inches of
vertical adaptability.
3. Attach the top and bottom brackets to your rack.
Connecting to the Power Source
To attach a power cord to the unit:
1. Plug the female end of the power cord firmly into its connector at the base.
2. Use a screwdriver to tighten the two screws on the retention bracket.
To connect to the power source:
Plug the male end of the power cord into the AC power source.
301-0399-3 Rev B. - Page 7
2. Installation
Connecting Devices
To avoid the possibility of noise due to arcing:
1. Keep the device’s on/off switch in the off position until after it is plugged into the outlet.
2. Connect devices to the outlets.
On 230V units, install a retention clip for each outlet; Pull the prongs out slightly and insert them into holes
on the sides, then insert the device’s power cord and snap the clip over the cord.
NOTE:
1. MGE UPS SYSTEMS recommends even distribution of attached devices across the all available outlets to
Specifications for more information.
2. The outlet retention clips provided with 230V units are designed for use with MGE UPS SYSTEMS’s IEC
60320/C13 to IEC 60320/C14 cable and may not properly fit 3rd party cables.
Always disconnect the power supply cord before opening to avoid electrical shock.
Afin d’éviter les chocs électriques, débranchez le cable électrique avant d’ouvrir.
Immer Netzleitung auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden.
Connecting the Sensors
The AmpMeter PDU may be equipped with two mini RJ11 T/H ports for attachment of the included
Temperature/Humidity sensor. Attach the mini RJ11 plug of the sensor(s) to the appropriate T/H port if
applicable.
Connecting to the Unit (Remote Monitoring Units Only)
Serial (RS232) port
AmpMeter PDU models may be equipped with an RJ45 Serial RS-232 port for attachment to a PC or networked
terminal server using the supplied RJ45 to RJ45 crossover cable and RJ45 to DB9F serial port adapter as
required. See Data Connections in Technical Specifications for more information on the Serial RS-232 port.
Ethernet port
AmpMeter PDU models may be equipped with an RJ45 10/100Base-T Ethernet port for attachment to an
existing network. This connection allows access via Telnet, Secure Shell (SSH) or a common web browser.
The unit configured with the following network defaults to allow unit configuration out-of-the-box through either
Telnet/SSH or via a web browser:
•
•
•
IP address:
Subnet Mask:
Gateway:
192.168.1.254
255.255.255.0
192.168.1.1
The local PC network connection must be configured as noted below:
NOTE: Contact your system administrator for instructions in reconfiguring the network connection.
Reconfiguration of your network connection may require a restart to take effect.
•
•
IP address:
Subnet Mask:
192.168.1.x (where x is 2-253)
255.255.255.0
Page 8 - 301-0399-3 Rev B.
3. Operations
Input Load...........................................................................................................................12
Sensors ...............................................................................................................................12
System.................................................................................................................................12
Network ...............................................................................................................................13
Telnet/SSH..........................................................................................................................13
HTTP/SSL...........................................................................................................................13
Serial Ports .........................................................................................................................14
Users....................................................................................................................................14
FTP ......................................................................................................................................15
SNTP ...................................................................................................................................16
SNMP ..................................................................................................................................16
Restart.................................................................................................................................17
User Administration ...........................................................................................................22
Serial Port Administration.................................................................................................25
System Administration ......................................................................................................26
TCP/IP Administration.......................................................................................................28
HTTP Administration .........................................................................................................30
Telnet Administration.........................................................................................................30
FTP Administration ............................................................................................................31
SNTP Administration.........................................................................................................32
301-0399-3 Rev B. - Page 9
3. Operations
This chapter contains information on commands and abilities available only in models equipped for remote
monitoring.
Interfaces
The AmpMeter PDU has two interfaces: the HTML interface accessed via the HTTP enabled Ethernet
connections and the command line for serial and Telnet connections.
Usernames and Passwords
The AmpMeter PDU has one predefined administrative user account (username/password: MGEUPS/MGEUPS)
and supports a maximum of 128 defined user accounts
NOTE: For security, MGE UPS SYSTEMS recommends removal of the predefined administrative user account
after a new account with administrative rights has been created.
Only an administrative-level user may perform operations such as creating/removing user accounts and command
privileges, changing passwords and displaying outlet and user information. An administrator may also view the
status of and control power to all outlets.
The administrator may create additional user accounts and then grant these users the right to view the status of
and control power to specific outlets, groups and ports.
Usernames may contain from 1 to 16 characters and are not case sensitive; spaces are not allowed. Passwords
may contain up to 16 characters, and are case sensitive.
Page 10 - 301-0399-3 Rev B.
3. Operations
HTML Interface
The HTML interface is constructed of three major components: the System Location bar, the User/Navigation
bar and the Control Screen. The System Location bar displays the AmpMeter PDU’s location and IP address
as well as the current Control Screen title. The User/Navigation bar displays the current user and privilege level
and provides access to all HTML pages. And the Control Screen is used to display current data and allow
changes to outlet states or system configuration.
The following sections describe each interface section/page and their use.
Figure 4. Example HTML page
Logging In
Logging in through HTML via a web browser requires directing a web client to the configured IP address of the
unit.
To log in by HTML:
1. In the login window, enter a valid username and password and press OK.
If you enter an invalid username or password, you will be prompted again.
You are given three attempts to enter a valid username and password combination. If all three fail, the
session ends and a protected page will be displayed.
301-0399-3 Rev B. - Page 11
3. Operations
Environmental Monitoring
The Environmental Monitoring section offers access to the Input Load page. This section is available to
administrative level users and users with Environmental Monitoring view rights.
Input Load
The Input Load page displays the AmpMeter PDU (s) absolute and descriptive name and the cumulative input
load in amperes of all devices attached to the AmpMeter PDU at the time the page was loaded. This page will
refresh automatically every 10 seconds.
Sensors
The Sensors page displays:
•
•
Temperature/humidity sensor’s absolute and descriptive names
Temperature/humidity sensor readings in degrees Celsius and percent relative humidity
Configuration
The Configuration section offers access to all unit configuration options including Network, Telnet/HTTP, Serial
Ports, Outlets, Groups, Users, FTP, Proxy/SNTP and SNMP. This section is available to administrative level
users only.
System
The System configuration page is used for reference of system information such as Ethernet NIC Serial Number,
Ethernet MAC address and system firmware and hardware revisions as well as assignment and maintenance of
the system location and tower descriptive names.
For description names, up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal –
spaces and colon characters are not allowed) are allowed.
NOTE: Spaces may be used for the location description only.
Creating a descriptive system location name:
Enter a descriptive name and press Apply.
Creating a descriptive unit name:
Click on the Tower Names link.
On the subsequent Tower Names page, enter a descriptive name and press Apply.
Creating descriptive input feed names:
Click on the Input Feed Names link.
On the subsequent Input Feed Names page, enter a descriptive name and press Apply.
Creating a descriptive Pass through port name:
Click on the Serial Port Names link which will open the Serial Ports configuration page. See Creating a
descriptive serial port name: on page 14 for additional information on creating descriptive Serial port names.
Creating a descriptive Environmental Monitor name:
Click on the Environmental Monitor Names link.
On the subsequent Environmental Monitor Names page, enter a descriptive name and press Apply.
Creating descriptive sensor names:
Click on the Sensor Names link.
On the subsequent Sensor Names page, enter a descriptive name and press Apply.
Page 12 - 301-0399-3 Rev B.
3. Operations
Network
The Network configuration page is used for maintenance of the network interface. From this page an
administrator may configure the IP address, subnet mask and gateway address as well as view the link status,
speed and duplex value.
The AmpMeter PDU is configured with the following network defaults to allow unit configuration out-of-the-box
through either Telnet or HTML:
•
•
•
IP address:
Subnet Mask:
Gateway:
192.168.1.254
255.255.255.0
192.168.1.1
The initial local PC network connection must be configured as noted below:
NOTE: Contact your system administrator for instructions in reconfiguring the network connection.
Reconfiguration of your network connection may require a restart to take effect.
•
•
IP address:
Subnet Mask:
192.168.1.x (where x is 2-253)
255.255.255.0
NOTE: The unit must be restarted after network configuration changes.
Setting the IP address, subnet mask or gateway:
In the appropriate field, enter the IP address, subnet mask or gateway address and press Apply.
Telnet/SSH
The Telnet/SSH configuration page used to enable or disable Telnet and SSH support and configure the port
Enabling or disabling Telnet or SSH support:
Select Enabled or Disabled from the appropriate Server drop-down menu and press Apply.
Changing the Telnet or SSH server port number:
In the appropriate Port field, enter the port number and press Apply.
HTTP/SSL
The HTTP/SSL configuration page used to enable or disable HTTP and SSL support, configure the port number
that the HTTP server watches and responds to, selection of the method of authentication used and SSL access
Enabling or disabling HTTP or SSL support:
Select Enabled or Disabled from the appropriate Server drop-down menu and press Apply.
Changing the HTTP server port number:
In the HTTP Port field, enter the port number and press Apply.
301-0399-3 Rev B. - Page 13
3. Operations
Setting the HTTP authentication method:
The AmpMeter PDU HTTP server supports two authentication methods for security and validation of the
username-password – Basic and MD5 digest.
The Basic method utilizes Base64 encoding to encode and deliver the username-password over the network to
the HTTP server for decoding and authentication. This basic method is supported by all web browsers and
offers a minimum level of security.
NOTE: The Base64 algorithm is widely-known and susceptible to packet-sniffer attack for acquisition of the
encoded username-password string.
The MD5 digest method provides stronger protection utilizing one-way encoded hash numbers, never placing
the username-password on the network. Instead, the sending browser creates a challenge code based on the
hash algorithm, provided username-password and unique items such as the device IP address and timestamp,
which is compared against the HTTP server internal user database of valid challenge codes. The MD5 digest
method offers a higher level of security than the Basic method but at present is not supported by all browsers.
NOTE: MD5 is known to be fully supported by Internet Explorer 5.0+, Navigator 7.0+ and Firefox 1.0+.
Select Basic or MD5 from the Authentication drop-down menu and press Apply.
Setting SSL access level
AmpMeter PDU SSL supports configuration of SSL connections as being either optional or required. The
default access level is set to optional.
•
•
Optional –Both non-secure (HTTP) and SSL encrypted connections (HTTPS) are allowed access.
Required – ONLY SSL encrypted connections (HTTPS) are allowed access.
Select Optional or Required from the Secure Access drop-down menu and press Apply.
Serial Ports
The Serial Ports configuration page is used for maintenance of the serial ports.
NOTE: Pass through connections may only be initiated from the command line interface via a Telnet/SSH
session.
Setting the data-rate for the serial ports:
Select the serial port data-rate from the drop-down menu and press Apply.
Creating a descriptive serial port name:
Click on the Edit link in the Action column next to the port to be configured.
On the subsequent Serial Port Edit page, enter the descriptive name. Up to 24 alphanumeric and other typeable
characters (ASCII 33 to 126 decimal, spaces and colon characters are not allowed) are allowed. Press Apply.
Enabling or disabling serial port active signal checking:
Click on the Edit link in the Action column next to the port to be configured.
On the subsequent Serial Port Edit page, select On or Off from the DSR Check drop-down menu and press Apply.
Users
The Users configuration page is used for creation and removal of usernames, assignment of accessible outlets
and group, assignment of privilege levels and the changing of user passwords.
Creating a new user:
Enter a user name in the Username field. Up to 24 alphanumeric and other typeable characters (ASCII 33 to
126 decimal, spaces and colon characters are not allowed) are allowed.
Enter a password for the new user and verify in the Password and Verify Password fields. For security,
password characters are not displayed. Press Apply.
Page 14 - 301-0399-3 Rev B.
3. Operations
Removing a user:
Click on the Remove link in the Action column for the user to be removed and press Yes on the subsequent
confirmation window.
Changing a user password:
Click on the Edit link in the Action column for the associated user.
On the subsequent User Edit page, enter a password and verify the new password for the new user in the
Password and Verify Password fields. For security, password characters are not displayed. Press Apply.
Changing a user’s access privilege level:
The AmpMeter PDU has four defined access privilege levels; Admin, User, On-Only and View-Only:
•
•
Admin:
User:
Full-access for all configuration, control (On, Off, Reboot), status and Pass through.
Partial-access for status and Pass through of assigned outlets, groups and serial
ports.
The administrator may also grant administrative privileges to other user accounts allowing the AmpMeter PDU to
have more than one administrative-level user.
NOTE: You cannot remove administrative privileges from the MGEUPS user unless another user has already
been given administrative access level privileges created.
Click on the Edit link in the Action column for the associated user.
On the subsequent User Edit page, select Admin, User, On-only or View-only from the Access Level
drop-down menu and press Apply.
Granting or removing Environmental Monitoring viewing privileges:
Click on the Edit link in the Action column for the associated user.
On the subsequent User Edit page, select Yes or No from the Environmental Monitoring drop-down menu and
press Apply.
Adding and Deleting serial port access:
Click on the Ports link in the Access column for the associated user.
On the subsequent User Ports page, select or deselect ports to be accessed by the user and press Apply.
FTP
The FTP configuration page is used for setup and maintenance of all settings required to perform an FTP
Setting the FTP Host IP Address:
Enter the IP address in the Host IP Address field and press Apply.
Setting the FTP username:
Enter the FTP server username in the Username field, and press Apply.
Setting the FTP password:
Enter the FTP server password in the Password field, and press Apply.
Setting the filepath:
Enter the path of the file to be uploaded in the Directory field, and press Apply.
Setting the filename for upload:
Enter the filename of the file to be uploaded in the Filename field, and press Apply.
301-0399-3 Rev B. - Page 15
3. Operations
Testing the FTP upload configuration:
This test validates that the unit is able to contact and log onto the specified FTP server, download the firmware
file and verify that the firmware file is valid for this unit.
Press Test.
SNTP
The SNTP configuration page is used for setup and maintenance of SNTP support.
Setting the SNTP Server Address:
Enter the IP address in the primary and/or secondary address field and press Apply.
SNMP
The SNMP configuration page is used for setup and maintenance of all settings required to enable SNMP
support as well as access to the trap configuration pages. For additional information on SNMP support and
detailed descriptions of available traps, see on page 34.
NOTE: Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap
condition, only the Tower Status trap is generated. Infeed and Outlet Status traps are suppressed until the
Tower Status returns to Normal.
Enabling or disabling SNMP support:
Select Enabled or Disabled from the drop-down menu and press Apply.
Setting the community strings:
Enter the community string in the appropriate field and press Apply.
Community strings may be 1 to 24 characters
Setting the trap timer:
Enter a trap timer value in the Error Trap Repeat Time field and press Apply.
The Error Trap Repeat Time value may be 1 to 65535 (in seconds).
Setting trap destinations:
Enter an IP address in the appropriate Trap Destination field and press Apply.
Enabling or disabling tower traps:
Click on the Tower Traps link.
On the subsequent Tower Traps page, select or deselect the desired traps and press Apply.
Configuring input feed traps:
Click on the Input Feed Traps link.
On the subsequent Input Feed Traps page, select or deselect the desired traps and press Apply.
For Load traps, enter a maximum load value for the infeed in the High Load Threshold field and press Apply.
The High Load Threshold value may be 0 to 255 (in amperes).
Page 16 - 301-0399-3 Rev B.
3. Operations
Tools
The Tools section contains access to rebooting the unit, uploading new firmware as well as resetting the unit to factory
defaults. This section is available to administrative level users only.
Restart
Performing a warm boot:
Select the Restart from the Action drop-down menu and press Apply.
Note: System user/outlet/group configuration or outlet states are NOT changed or reset with this command.
Resetting to factory defaults:
See To reset to factory defaults from the HTML interface on page 46 for more information on resetting a AmpMeter
PDU to factory defaults from the HTML interface.
Uploading new firmware:
See Uploading Firmware on page 46 for more information on uploading new firmware from the HTML interface.
301-0399-3 Rev B. - Page 17
3. Operations
Command Line Interface
Logging In
Logging in through Telnet requires directing the Telnet client to the configured IP address of the unit.
Logging in through the Console (RS232) port requires the use of a terminal or terminal emulation software
configured to support ANSI or VT100 and a supported data rate (300, 1200, 2400, 4800, 9600, 19200, 38400,
57600, or 115200 BPS) - 8 data bits-no parity-one stop bit and Device Ready output signal (DTR or DSR).
To log in by RS-232 or Telnet:
1. Press Enter. The following appears, where x.xx is the firmware version:
AmpMeter PDU Version x.xx
Username:
NOTE: Logging in by Telnet will automatically open a session. It is not necessary to press Enter.
2. At the Username: and Password: prompts, enter a valid username and password. And press Enter.
You are given three attempts to enter a valid username and password combination. If all three fail, the
session ends.
When you enter a valid username and password, the command prompt (AmpMeter PDU:) appears. If a location
identifier was defined, it will be displayed before the AmpMeter PDU: prompt. See Creating a location
You may enter commands in any combination of uppercase and lowercase. You must enter all command
characters correctly; there are no command abbreviations. There are two types of commands: operations and
administration. A user must have administrative privileges to use the administration commands. The following
tables list and briefly describe each command.
Operations Command Summary
Command
ILoad
Description
Displays the cumulative input load per branch or phase
Displays the status of the infeeds
Connects to a serial port
Istat
Connect
Login
Ends the current session and brings up the Username: prompt
Ends a session
Logout
Quit
Ends a session
List Ports
Lists all accessible serial ports for the current user
Administrative Command Summary
Add Porttouser
Create User
Delete Portfromuser
List User
Grants a user access to one or all serial ports
Adds a user account
Removes access to one or all serial ports
Displays all accessible outlets/groups/ports for a user
Displays privilege levels for all users
Deletes a user account
List Users
Remove User
Restart
Performs a warm boot
Set Envmon Name
Specifies a descriptive field for the integrated Environmental Monitor
Set Envmon THS Name Specifies a descriptive field for a temperature-humidity sensor
Page 18 - 301-0399-3 Rev B.
3. Operations
Administrative Command Summary (continued)
Set FTP Filename
Set FTP Filepath
Set FTP Host
Specifies the file to be uploaded via FTP
Specifies the filepath for the file to be uploaded
Sets the FTP Host IP address
Set FTP Password
Set FTP Username
Set Gateway
Sets the password for the FTP Host
Sets the username for the FTP Host
Sets the Gateway
Set Infeed Name
Set Ipaddress
Set Location
Specifies a descriptive field for the infeed
Sets the IP address
Specifies a descriptive field for the HTML control screen and login banner
Sets the Subnet Mask
Set Subnet Mask
Set Telnet Port
Set Telnet
Sets the Telnet server port number
Enables or disables Telnet access
Set Tower Name
Set User Access
Set User Envmon
Set User Password
Set Port Name
Set Port Dsrchk
Set Port Speed
Show FTP
Specifies a descriptive field for the AmpMeter PDU
Sets the access level for a user
Grants or removes privileges to view input and environmental monitoring status
Changes the password for a user
Specifies a descriptive field for a serial port
Sets the DSR active signal checking for a serial port
Set the connection speed for all serial ports
Displays FTP configuration information
Show Infeeds
Show Network
Show Ports
Displays infeed configuration information
Display network configuration information
Displays serial port configuration information
Displays system configuration information
Displays tower configuration information
Displays the AmpMeter PDU firmware version
Show System
Show Towers
Version
To display the names of commands that you may execute:
At the command prompt, press Enter. A list of valid commands for the current user appears.
301-0399-3 Rev B. - Page 19
3. Operations
Operations Commands
Operations commands provide information about the AmpMeter PDU environment and control session
operations.
Displaying accessible serial ports
The List Ports command displays accessible serial ports for the current user.
To display accessible serial ports:
At the AmpMeter PDU: prompt, type list ports and press Enter.
Example
The follow command displays all accessible serial ports for the current user:
AmpMeter PDU: list ports<Enter>
Port
ID
Port
Name
Console
Console
Displaying infeed status
The Istat or Iload command displays the status of one or more infeed.
This display includes the infeed absolute and descriptive names and the Input Status and current Load reported
to the AmpMeter PDU by the infeed.
To display status of one or more infeeds:
Type istat and press Enter, or
Type iload and press Enter.
Examples
The following command displays the infeed status:
AmpMeter PDU: istat
Input
Feed ID Feed Name
Input
Input
Status
Input
Load
.AA
HQ_1_Infeed_A
On
10.5 Amps
Connecting to a serial device
The Connect command allows Pass through serial connection to devices attached to the standard serial port
(Console).
To connect to a serial device:
At the AmpMeter PDU: prompt, type connect console and press Enter.
To disconnect from a serial device:
Type: !*break and press Enter.
Page 20 - 301-0399-3 Rev B.
3. Operations
Displaying the status of the Environmental Monitor
The Envmon command displays the status of the integrated Environmental Monitor.
By default, only administrative user accounts are allowed access to the Envmon command. An administrator
may user the Set User Envmon command to enable and disable access for other user accounts.
To display the status of the Environmental Monitor:
At the AmpMeter PDU: prompt, type envmon and press Enter.
Example
The following command displays the status of the Environmental Monitor.
AmpMeter PDU: envmon<Enter>
Environmental Monitor .A
Name: Florida_HQ_1
Status: Normal
Temperature/Humidity Sensors
ID
.A1
.A2
Name
Temperature
Not Found
23.5 Deg. C
Humidity
Not Found
22 % RH
Temp_Humid_Sensor_A1
T/H2_Florida_HQ_1
Starting a new session
The Login command activates the Username: prompt. The current session ends, allowing a user to log in and
start a new session under a different username.
To start a new session:
At the AmpMeter PDU: prompt, type login and press Enter. The Username: prompt appears.
Ending a session
The Quit or Logout commands ends a session. A session ends automatically when no activity is detected for
five minutes, or upon loss of connection.
To end a session:
At the AmpMeter PDU: prompt, type quit and press Enter, or
Type logout and press Enter.
301-0399-3 Rev B. - Page 21
3. Operations
Administration Commands
Administration commands may only be issued by a user with administrative privileges, such as the predefined
MGEUPS user or another user who has been granted administrative privileges with the Set User MGEUPSpriv
command.
User Administration
Creating a user account
The Create User command creates a user account with the specified username and password. See Usernames
and Passwords in this chapter for more information.
To create a user account:
At the AmpMeter PDU: prompt, type create user, optionally followed by a 1-16 character username (Spaces
are not allowed, and usernames are not case sensitive). Press Enter.
At the Password: prompt, type a password of up to 16 alphanumeric and other typeable characters (ASCII 32 to
126 decimal). Passwords are case sensitive. Press Enter. To specify no password, press Enter at the
prompt.
At the Verify Password: prompt, retype the password. Press Enter. To verify no password, press Enter at the
prompt.
Example
The following command creates the user account JaneDoe:
AmpMeter PDU: create user JaneDoe<Enter>
Password: <Enter>
Verify New Password: <Enter>
For security, password characters are not displayed.
Removing a user account
The Remove User command removes a user account.
NOTE: You may remove the predefined user account MGEUPS only if another user account has been granted
administrative privileges using the Set User MGEUPSpriv command.
To remove a user account:
At the AmpMeter PDU: prompt, type remove user, optionally followed by a username. Press Enter.
Page 22 - 301-0399-3 Rev B.
3. Operations
Changing a password
The Set User Password command changes a user’s password. For security, when you type a password, the
To change a password:
At the AmpMeter PDU: prompt, type set user password, followed by a username and press Enter.
At the Password: prompt, type the new password and press Enter. Passwords may contain up to 16
characters, and spaces are not allowed. To specify no password, press Enter at the prompt.
At the Verify Password: prompt, retype the new password and press Enter. To verify no password, press
Enter at the prompt.
Examples
The following command changes the password for the user JohnDoe:
AmpMeter PDU: set user password johndoe<Enter>
Password: <Enter>
Verify Password: <Enter>
The following command blanks the password for the user JaneDoe:
AmpMeter PDU: set user password<Enter>
Username: janedoe<Enter>
Password: <Enter>
Verify Password: <Enter>
Setting user access level privileges
The Set User Access command sets the access level privileges for a user. The AmpMeter PDU has two
defined access privilege levels; Admin, User. For more information on user access levels, see Changing a
The administrator may also grant administrative privileges to other user accounts allowing the AmpMeter PDU to
have more than one administrative-level user.
NOTE: You cannot remove administrative privileges from the MGEUPS user unless another user has already
been given administrative access level privileges created.
To set the access level privilege for a user:
At the AmpMeter PDU: prompt, type set user access, followed by admin, or user, optionally followed by a
username and press Enter.
Examples
The following command sets the user access level for JohnDoe to Admin:
AmpMeter PDU: set user access admin johndoe<Enter>
The following command sets the user access level for JaneDoe to User:
AmpMeter PDU: set user access user janedoe<Enter>
301-0399-3 Rev B. - Page 23
3. Operations
Granting and removing input status viewing privileges
The Set User Envmon command grants or removes input status viewing privileges to/from a user.
NOTE: This command also grants or removes viewing privileges for the status of the optional Equipment
Cabinet Environmental Manager and attached sensors. See the Equipment Cabinet Environmental Manager
Installation and Operations manual for more information.
To grant or remove input status viewing privileges for a user:
At the AmpMeter PDU: prompt, type set user envmon followed by on or off, optionally followed by a
username and press Enter.
Example
The following command grants intput status viewing privileges to the user JohnDoe:
AmpMeter PDU: set user envmon on johndoe<Enter>
Displaying the access privilege levels
The List Users command displays all defined users with their access privilege level.
To display user access privilege levels:
At the AmpMeter PDU: prompt, type list users and press Enter.
Example
The following command displays all users with their access privilege level:
AmpMeter PDU: list users<Enter>
User
Name
Privilege
Level
Environmental
Monitoring
JOHNDOE
JANEDOE
Admin
User
Allowed
Not Allowed
Adding serial port access to a user
The Add PortToUser command grants a user access to the serial port.
To grant serial port access to a user:
At the AmpMeter PDU: prompt, type add porttouser console and a username. Press Enter.
Deleting serial port access for a user
The Delete PortFromUser command removes a user’s access to the serial port. You cannot remove access to
the serial port for an administrative level user.
To delete serial port access for a user:
At the AmpMeter PDU: prompt, type delete portfromuser console and a username. Press Enter.
Page 24 - 301-0399-3 Rev B.
3. Operations
Displaying user serial port access
The List User command displays all ports for a user.
To display user serial port access:
At the AmpMeter PDU: prompt, type list user, optionally followed by a username. Press Enter.
Example
The following command displays information about the user JaneDoe:
AmpMeter PDU: list user janedoe<Enter>
Username: JANEDOE
Ports:
Port
ID
Port
Name
Console
Console
JaneDoe may access the Console serial port.
Serial Port Administration
Creating a descriptive serial port name
The Set Port Name command assigns a descriptive name to a serial port. You may use this name in
commands that require a port name as an alternative to using the port’s absolute name.
To create a port name:
At the AmpMeter PDU: prompt, type set port name, followed by the absolute outlet name and a descriptive
name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not
allowed). Port names are not case sensitive. Press Enter.
Example
The following command adds the descriptive name Rack1 to Console port:
AmpMeter PDU: set port name console Rack1<Enter>
Setting the serial ports data-rate
The Set Port Speed command sets the default data-rate for the serial port.
Valid data-rates are 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200.
To set the serial port data-rate:
At the AmpMeter PDU: prompt, type set port speed, follow by the data-rate and press Enter.
Example
The following command sets the serial ports data-rate to 38400 BPS:
AmpMeter PDU: set port speed 38400<Enter>
Enabling or disabling active signal checking for serial connections
The Set Port Dsrchk command enables or disables active signal checking for serial connections to devices
attached to any of the available serial ports.
To enable or disable active signal checking for serial connections:
At the AmpMeter PDU: prompt, type set port dsrchk console, on or off, and press Enter.
301-0399-3 Rev B. - Page 25
3. Operations
Displaying serial port information
The Show Ports command displays information about all serial ports. This information includes:
•
•
•
Serial port data rate
Descriptive port name, if applicable
DSR signal checking settings
To display serial port information:
At the AmpMeter PDU: prompt, type show ports and press Enter.
Example
The following command displays all serial port information:
AmpMeter PDU: show ports<Enter>
Serial Port Configuration
ALL Ports:
Baud Rate: 38400
Console Port:
DSR Check: ON
System Administration
Creating a location description
The Set Location command specifies text that appears in the HTML control screen’s Location field. The text is
also appended to a Welcome to banner that appears when a user successfully logs in serially or through a
Telnet session.
If you do not issue this command, or if you issue this command without specifying any text, the control screen ’s
Location field will be blank and no Welcome to banner will be displayed.
To create a location description:
At the AmpMeter PDU: prompt, type set location, followed by a descriptive name of up to 24 alphanumeric
and other typeable characters (ASCII 32 to 126 decimal - spaces are allowed). Press Enter.
Omitting any characters after typing ‘set location’ deletes any previously specified text.
Examples
The following command specifies Florida HQ as the descriptive location for the control screen and the login
banner:
AmpMeter PDU: set location Florida HQ<Enter>
The following command deletes any previously specified location description:
AmpMeter PDU: set location<Enter>
In this case, the control screen’s Location field will be blank, and no welcome banner will be displayed after a
successful login.
Page 26 - 301-0399-3 Rev B.
3. Operations
Displaying system configuration information
The Show System command displays all system configuration information.
•
•
•
•
•
Firmware version
NIC module serial number and MAC address
Hardware revision code and Flash size
Uptime since last system restart
System location description
See 0on page 32 for more information on SNMP.
To display system configuration information:
At the AmpMeter PDU: prompt, type show system and press Enter.
Example
System Information
F/W Version:
NIC S/N:
AmpMeter PDU Version 5.2i
1600001
MAC Address:
00-0a-9c-10-00-01
H/W Rev Code: 0
Flash Size:
Uptime:
1 MB
0 days 6 hours 14 minutes 1 second
Location:
Florida HQ
Creating a descriptive tower name
The Set Tower Name command assigns a descriptive name to a tower. This descriptive name is displayed
command.
To create a tower name:
At the AmpMeter PDU: prompt, type set tower name, followed by the absolute tower name, then the
descriptive name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces
are not allowed). Press Enter.
Examples
The following command adds the descriptive name Florida_HQ_1 to tower .a:
AmpMeter PDU: set tower name .a Florida_HQ_1<Enter>
Displaying tower information
The Show Towers command displays information about the AmpMeter PDU. This information includes the
absolute and descriptive AmpMeter PDU names.
To display tower information:
At the AmpMeter PDU: prompt, type show towers and press Enter.
Example
AmpMeter PDU: show towers<Enter>
Tower
ID
Tower
Name
.A
Florida_HQ_1
301-0399-3 Rev B. - Page 27
3. Operations
Creating a descriptive infeed name
The Set Infeed Name command assigns a descriptive name to an infeed. This descriptive name is displayed
when the Show Traps command is issued.
To create a infeed name:
At the AmpMeter PDU: prompt, type set infeed name, followed by the absolute infeed name, then the
descriptive name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces
are not allowed). Press Enter.
Example
The following command adds the descriptive name HQ_1_Infeed_A to the infeed on the AmpMeter PDU:
AmpMeter PDU: set infeed name .aa HQ_1_Infeed_A<Enter>
Displaying Infeed information
The Show Infeeds command displays information about all infeeds. This information includes the absolute and
descriptive infeed names.
To display tower information:
At the AmpMeter PDU: prompt, type show infeeds and press Enter.
Example
AmpMeter PDU: show infeeds<Enter>
Input
Input
Feed ID Feed Name
.AA
.AB
.BA
.BB
HQ_1_Infeed_A
HQ_1_Infeed_B
HQ_2_Infeed_A
HQ_2_Infeed_B
Displaying the firmware version
The Version command displays the firmware version.
To display the firmware version:
At the AmpMeter PDU: prompt, type version and press Enter.
Performing a warm boot
The Restart command performs a warm boot of the AmpMeter PDU.
NOTE: System user/outlet/group/port configuration or outlet states are NOT changed or reset with this
command.
To perform a warm boot:
At the AmpMeter PDU: prompt, type restart and press Enter.
TCP/IP Administration
NOTE: A restart of the AmpMeter PDU is required after setting or changing ANY TCP/IP configurations. See
Setting the IP address
The Set Ipaddress command sets the TCP/IP address of the network interface controller.
To set the IP address:
At the AmpMeter PDU: prompt, type set ipaddress, followed by the IP address and press Enter.
Example
The following command sets the IP address to 12.34.56.78:
AmpMeter PDU: set ipaddress 12.34.56.78<Enter>
Page 28 - 301-0399-3 Rev B.
3. Operations
Setting the subnet mask
The Set Subnet command sets the subnet mask for the network the PT40 will be attached to.
To set the subnet mask:
At the AmpMeter PDU: prompt, type set subnet, followed by the subnet mask and press Enter.
Example
The following command sets the subnet mask to 255.0.0.0
AmpMeter PDU: set subnet 255.0.0.0<Enter>
Setting the gateway
The Set Gateway command sets the IP address of the default gateway the AmpMeter PDU uses to access
external networks.
To set the gateway IP address:
At the AmpMeter PDU: prompt, type set gateway, followed by the gateway IP address and press Enter.
Example
The following command set the gateway IP address to 12.34.56.1:
AmpMeter PDU: set gateway 12.34.56.1<Enter>
Displaying network configuration information
The Show Network command displays TCP/IP, Telnet, SSH, Web, SSL and SNMP configuration information.
•
•
•
•
•
IP address, subnet mask and gateway
Enabled-disabled status of Telnet, SSH, HTTP,SSL and SNMP support
Telnet, SSH, and HTTP port numbers
HTTP authentication method and SSL access setting
Network status
See page 32 for more information on SNMP and Secure Proxy
To display network configuration information:
At the AmpMeter PDU: prompt, type show network and press Enter.
Example
The following command displays the network configuration information:
AmpMeter PDU: show network<Enter>
Network Configuration
IP Address:
Subnet Mask:
Gateway:
12.34.56.78
255.0.0.0
12.34.56.1
Telnet:
SSH:
HTTP:
SSL:
Enabled
Enabled
Enabled
Enabled
Enabled
Port:
Port: 65535
Port: 80
23
Security: BASIC
Access: Required
SNMP:
Network Status
Link:
Up
Speed:
Duplex:
Negotiation:
100 Mbps
Full
Auto
301-0399-3 Rev B. - Page 29
3. Operations
HTTP Administration
NOTE: A restart is required after setting or changing ANY Telnet/Web configurations. See Performing a warm
Enabling and disabling HTTP support
The Set HTTP command is used to enable or disable HTTP support.
To enable or disable HTTP support:
At the AmpMeter PDU: prompt, type set http, followed by enabled or disabled and press Enter.
Changing the HTTP server port
With HTTP support enabled, the HTTP server watches and responds to requests on the default HTTP port number 80.
This port number may be changed using the Set HTTP Port command.
To change the HTTP port:
At the AmpMeter PDU: prompt, type set http port, followed by the port number and press Enter.
Example
The following changes the HTTP port number to 2048:
AmpMeter PDU: set HTTP port 2048<Enter>
Setting the HTTP authentication method
The Set HTTP Security command is used to set the method of authentication. The AmpMeter PDU HTTP server
supports two authentication methods for security and validation of the username-password – Basic and MD5 digest.
For more information on authentication methods, see Setting the HTTP authentication method: on page 14.
To set the HTTP authentication method:
At the AmpMeter PDU: prompt, type set http security, followed by basic or md5 and press Enter.
Telnet Administration
NOTE: A restart of the AmpMeter PDU is required after setting or changing ANY Telnet/Web configurations.
Enabling and disabling Telnet support
The Set Telnet command is used to enable or disable Telnet support.
To enable or disable Telnet support:
At the AmpMeter PDU: prompt, type set telnet, followed by enabled or disabled and press Enter.
Changing the Telnet port
With Telnet support enabled, the Telnet server watches and responds to requests on the default Telnet port number 23.
This port number may be changed using the Set Telnet Port command.
To change the Telnet socket:
At the AmpMeter PDU: prompt, type set telnet port, followed by the port number and press Enter.
Example
The following changes the Telnet port number to 7001:
AmpMeter PDU: set telnet port 7001<Enter>
Page 30 - 301-0399-3 Rev B.
3. Operations
FTP Administration
You may upload new versions of firmware into the AmpMeter PDU using File Transfer Protocol (FTP). This allows
access to new firmware releases for firmware improvements and new features additions. The following
commands are used to configure the AmpMeter PDU for an FTP firmware upload. See 0Uploading Firmware for
more information on initiating a FTP firmware upload.
Setting the FTP Host IP address
The Set FTP Host command sets the FTP host IP address allowing for firmware file uploads.
To set the FTP Host IP address:
At the AmpMeter PDU: prompt, type set ftp host, followed by the Host IP address and press Enter.
Example
The following command sets the FTP Host IP address to 12.34.56.99:
AmpMeter PDU: set ftp host 12.34.56.99<Enter>
Setting the FTP username
The FTP Username command sets the username as required by the FTP Host.
To set the FTP username:
At the AmpMeter PDU: prompt, type set ftp username, followed by the FTP username and press Enter.
Example
The following command sets the FTP username to Guest:
AmpMeter PDU: set ftp username guest<Enter>
Setting the FTP Password
The FTP Password command sets the password as required by the FTP Host.
To set the FTP password:
At the AmpMeter PDU: prompt, type set ftp password, followed by the FTP password and press Enter.
Example
The following command sets the FTP password to OpenSesame:
AmpMeter PDU: set ftp password OpenSesame<Enter>
Setting the filename to be uploaded
The FTP Filename command sets the filename of the firmware file to be uploaded.
To set the FTP filename:
At the AmpMeter PDU: prompt, type set ftp filename, followed by the firmware filename and press Enter.
Example
The following command sets the FTP filename to snb_s53a.bin:
AmpMeter PDU: set ftp filename snb_s53a.bin<Enter>
Setting the filepath for the file to be uploaded
The FTP Filepath command sets the filepath for the firmware file to be uploaded.
To set the FTP filepath:
At the AmpMeter PDU: prompt, type set ftp filepath, followed by the filepath and press Enter.
Example
301-0399-3 Rev B. - Page 31
3. Operations
Displaying FTP configuration information
The Show FTP command displays all FTP configuration information.
•
•
•
FTP Host IP address
FTP Host username and password
Firmware filepath and filename
To display FTP configuration information:
At the AmpMeter PDU: prompt, type show ftp and press Enter.
Example
The following command displays the FTP configuration information:
AmpMeter PDU: show ftp<Enter>
FTP Configuration
Host IP Address: 12.34.56.99
Username:
Password:
Directory:
Filename:
guest
OpenSesame
snb_s53a.bin
SNTP Administration
AmpMeter PDU supports the use of a network time service to provide a synchronized time reference.
Setting the SNTP server address
The Set SNTP command is used to set the primary and secondary SNTP server addresses.
To set the SNTP server address:
At the AmpMeter PDU: prompt, type set sntp, followed by primary or secondary, and the SNTP server IP
address. Press Enter.
Example
The following command set the primary SNTP server address to 204.152.184.72:
AmpMeter PDU: set sntp primary 204.152.184.72<Enter>
Displaying SNTP configuration information
The Show SNTP command displays all SNTP configuration information.
To display SNTP configuration information
At the AmpMeter PDU: prompt, type show sntp and press Enter.
Example
The following command displays the SNTP configuration information:
AmpMeter PDU: show sntp <Enter>
SNTP Date/Time (GMT): 2003-02-21 21:32:48
SNTP Primary IP Address:
204.152.184.72
SNTP Secondary IP Address: 0.0.0.0
Page 32 - 301-0399-3 Rev B.
4. Advanced Operations
This chapter contains information on commands and abilities available only in models equipped for remote
monitoring.
SSL
Secure Socket Layers (SSL) version 3 enables secure HTML sessions between a AmpMeter PDU Remote
Power Manager and a remote user. SSL provides two chief features designed to make TCP/IP (Internet)
transmitted data more secure:
•
•
Authentication – The connecting client is assured of the identity of the server.
Encryption – All data transmitted between the client and the server is encrypted rendering any
intercepted data unintelligible to any third party.
SSL uses the public-and-private key encryption system by RSA, which also requires the use of digital
certificates. An SSL Certificate is an electronic file uniquely identifying individuals or websites and enables
encrypted communication; SSL Certificates serve as a kind of digital passport or credential. The AmpMeter
PDU product’s SSL Certificate enables the client to verify the AmpMeter PDU’s authenticity and to
communicate with the AmpMeter PDU securely via an encrypted session, protecting confidential information
from interception and hacking.
SSL Command Summary
Command
Set SSL
Description
Enables/disables SSL support
Sets SSL access as optional or required
Set SSL access
Enabling and Setting up SSL Support
NOTE: A restart of the AmpMeter PDU is required after setting or changing ANY SSL configurations. See
Enabling or disabling SSL support
The Set SSL command is used to enable or disable SSL support.
To enable or disable SSL support:
At the AmpMeter PDU: prompt, type set ssl, followed by enabled or disabled and press Enter.
Setting SSL access level
The Set SSL Access command is used to assign use of SSL as optional or required. The default access level
is set to optional.
To change the access level:
At the AmpMeter PDU: prompt, type set ssl access, followed optional or required, and press Enter.
Example
The following changes the access level to required:
AmpMeter PDU: set ssl access required<Enter>
SSL Technical Specifications
Secure Socket Layer (SSL) version 3
Transport Layer Security (TLS) version 1 (RFC 2246)
SSL/TLS-enabled HTTPS server (RFC 2818)
Self-Signed X.509 Certificate version 3 (RFC 2459)
Asymmetric Cryptography:
1024-bit RSA Key Exchange
Symmetric Cryptography Ciphers:
TLS_RSA_WITH_AES_256_CBC_SHA
TLS_RSA_WITH_AES_128_CBC_SHA
TLS_RSA_WITH_3DES_EDE_CBC_SHA
TLS_RSA_WITH_DES_CBC_SHA
Page 34 - 301-0399-3 Rev B.
4. Advanced Operations
SSH
Secure Shell (SSH) version 2 enables secure network terminal sessions between a AmpMeter PDU Remote
Power Manager and a remote user over insecure network. SSH provides an encrypted terminal sessions with
strong authentication of both the server and client, using public-key cryptography and is typically used as a
replacement for unencrypted Telnet. In addition to enabling secure network terminal sessions to the AmpMeter
PDU for configuration and power management, the SSH session may be used for secure Pass through
connections to attached devices.
SSH requires the configuration and use of a client agent on the client PC. There are many freeware, shareware
or for-purchase SSH clients available. Two examples are the freeware client PuTTY and the for-purchase client
SecureCRT ® by VanDyke® Software. For configuration and use of these clients, please refer to the applicable
software documentation.
SSH Command Summary
Command
Set SSH
Description
Enables/disables SSH support
Sets the SSH server port number
Set SSH port
Enabling and Setting up SSH Support
NOTE: A restart of the AmpMeter PDU is required after setting or changing ANY SSH configurations. See
Enabling or disabling SSH support
The Set SSH command is used to enable or disable SSH support.
To enable or disable SSH support:
At the AmpMeter PDU: prompt, type set ssh, followed by enabled or disabled and press Enter.
Changing the SSH server port
With SSH support enabled, the SSH server watches and responds to requests on the default SSH port number
22. This port number may be changed using the Set SSH Port command.
To change the SSH port:
At the AmpMeter PDU: prompt, type set ssh port, followed by the port number and press Enter.
Example
The following changes the SSH port number to 65535:
AmpMeter PDU: set ssh port 65535<Enter>
SSH Technical Specifications
Secure Shell (SSH) version 2
Asymmetric Cryptography:
Diffie-Hellman DSA/DSS 512-1024 (random) bits per NIST specification
Symmetric Cryptography:
AES256-CBC
AES192-CBC
AES128-CBC
RIJNDAEL256-CBC
RIJNDAEL192-CBC
RIJNDAEL128-CBC
3DES-192-CBC
BLOWFISH-128-CBC
ARCFOUR-128
Message Integrity:
HMAC-SHA1-160
HMAC-MD5-128
HMAC-SHA1-96
HMAC-MD5-96
Authentication:
Username/Password
Session Channel Break Extension (for RS232 Break)
301-0399-3 Rev B. - Page 35
4. Advanced Operations
SNMP
The AmpMeter PDU family of products supports the Simple Network Management Protocol (SNMP). This
allows network management systems to use SNMP requests to retrieve information and control power for the
individual outlets.
The AmpMeter PDU includes an SNMP v1 agent supporting standard MIB I and MIB II objects.
NOTE: For security, SNMP support is disabled by default.
SNMP Command Summary
Command
Description
Set snmp
Enables or disables SNMP support
Sets the ‘get’ community string
Set snmp getcomm
Set snmp setcomm
Set snmp trapdest1
Set snmp trapdest2
Set snmp traptime
Show snmp
Sets the ‘set’ community string
Sets a destination IP addresses for traps
Sets a destination IP addresses for traps
Sets the delay for steady state condition traps
Displays all SNMP configuration information
Enabling and Setting up SNMP Support
AmpMeter PDU SNMP support must be enabled and configured for access to AmpMeter PDU3 MIB objects
and generation of all AmpMeter PDU3 traps.
Enabling/disabling SNMP support
The AmpMeter PDU SNMP command is used to enable or disable SNMP support.
To enable SNMP support:
At the AmpMeter PDU: prompt, type set snmp, followed by enabled or disabled and press Enter.
NOTE: A restart of the AmpMeter PDU is required after enabling or disabling SNMP support. See Performing
Setting trap destinations
The Set SNMP Trapdest1 and Trapdest2 commands are used to set the IP addresses of SNMP management
stations receiving all traps. AmpMeter PDU supports a maximum of two trap destinations; one must be defined
to enable trap generation.
To set the trap destination:
At the AmpMeter PDU: prompt, type set snmp, trapdest1 or trapdest2, the Ipaddress and press Enter.
Example
The following sets the trap destination 1 to 64.42.31.208:
AmpMeter PDU: set snmp trapdest1 64.42.31.208<Enter>
To reset the trap destination:
At the AmpMeter PDU: prompt, type set snmp, trapdest1 or trapdest2, 0.0.0.0 and press Enter.
Page 36 - 301-0399-3 Rev B.
4. Advanced Operations
Setting the trap timer
The Set Traptime command sets the timer period between repeated error-condition traps. The valid range for
the timer period is 1 to 65535 (in seconds).
The default value for the timer period is 60 seconds.
To set the trap timer:
At the AmpMeter PDU: prompt, type set traptime, followed by the timer period and press Enter.
Example
The following sets the timer period to 180 seconds:
AmpMeter PDU: set traptime 180<Enter>
Setting the Get/Set community strings
AmpMeter PDU supports two SNMP community strings that provide varying levels of access to objects defined
in the AmpMeter PDU3 MIB.
Community strings may be 1 to 24 characters.
Setcomm
The Setcomm string provides read-write access to AmpMeter PDU3 MIB objects.
The default Setcomm string is “private”
To set the Setcomm community string:
At the AmpMeter PDU: prompt, type set snmp setcomm, followed by the string and press Enter.
Getcomm
The Getcomm string provides read-only access to AmpMeter PDU3 MIB objects.
The default Getcomm string is “public”.
To set the Getcomm community string:
At the AmpMeter PDU: prompt, type set snmp getcomm, followed by the string and press Enter.
Setting the Trap community string
The Set SNMP Trapcomm command is used to set the community string that is included with all generated
traps. This string must be defined to enable trap generation.
The trap community string may be 1 to 24 characters.
The default Trapcomm string is “trap”.
To set the Trapcomm community string:
At the AmpMeter PDU: prompt, type set snmp trapcomm, followed by the string and press Enter.
301-0399-3 Rev B. - Page 37
4. Advanced Operations
Displaying SNMP configuration information
The Show SNMP command displays all SNMP configuration information.
•
•
•
•
SNMP support status
SNMP community strings
Trap timer value
Trap destinations
To display SNMP configuration information:
At the AmpMeter PDU: prompt, type show snmp and press Enter.
Example
The following command displays the SNMP configuration information:
AmpMeter PDU: show snmp<Enter>
SNMP Configuration
SNMP:
Enabled
private
public
trap
SET Community String:
GET Community String:
TRAP Community String:
Error Trap Repeat Time (seconds): 180
Trap Destination 1:
Trap Destination 2:
64.42.31.208
(undefined)
SNMP Traps
The AmpMeter PDU supports three types of SNMP traps. Traps are enabled at the tower (T), infeed (I) or
outlet (O) level.
Trap Summary
Name Level(s) Description
Status T, I, O
Operational status change
Control status change
Input load out of limit
Change
Load
O
I
All traps include the Location of the AmpMeter PDU as defined with the Set Location command. See Creating a
location description on page 12 for more information.
Status trap
A Status trap is generated when an error condition occurs on a tower, infeed or outlet. Status traps include the
reported Status, the Location of the AmpMeter PDU, and identifier and name of the affected tower, infeed or
outlet.
Any Trap Status generates a Status trap and triggers the trap timer. A new trap is generated at the end of
every timer period until the Status returns to a non-error status.
Tower Status traps
Status
Error
Description
Normal
NoComm
Tower is working correctly
Communication to the tower has been lost
x
Infeed Status traps
Status
On
Error
Description
Infeed is on
OffError
NoComm
x
x
Infeed should be on but no current is sensed at the infeed
Communication to the infeed has been lost
Page 38 - 301-0399-3 Rev B.
4. Advanced Operations
Environmental Monitor Status traps
Status
Error
Description
Normal
NoComm
The Environmental Monitor is working correctly
x
Communication to the Environmental Monitor has been lost
Temperature/Humidity Sensor Status traps
Status
Found
Error
Description
The sensor has been detected
NotFound
Lost
No sensor has been detected
x
x
Sensor initially detected but communication to the sensor has been lost
Communication to the sensor has been lost
NoComm
NOTE: Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap
condition, only the Tower Status trap is generated. Infeed and Outlet Status traps are suppressed until the
Tower Status returns to Normal.
Change trap
The Change trap is generated for all outlet status changes between any on/off conditions. Change traps
include the outlet status, Location of the AmpMeter PDU, and identifier and name of the affected outlet. For
descriptions of the outlet status types, please refer to the prior table.
Load Trap
The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load traps
include the reported input load, load status, Location of the AmpMeter PDU, and identifier and name of the
affected infeed.
Any error state generates a Load trap and triggers the trap timer. A new trap is generated at the end of every
timer period until the Load returns to a non-error status.
Load traps
Status
Error
Description
Normal
Infeed is on and within preset thresholds
Infeed is off
NotOn
Reading
LoadHigh
OverLoad
ReadError
NoComm
Non-error state – Load status currently being read
Infeed current load exceeds preset threshold
Infeed current load exceeds the measurable range for the infeed
Unable to read Load status
x
x
x
x
Communication to the infeed has been lost
301-0399-3 Rev B. - Page 39
4. Advanced Operations
Temp Trap
The Temp trap is generated whenever the temperature on a temperature/humidity sensor is beyond preset
thresholds. Temp traps include the reported temperature, temp status, Location of the AmpMeter PDU, and
identifier and name of the affected sensor.
Any error state generates a Temp trap and triggers the trap timer. A new trap is generated at the end of every
timer period until the Temp returns to a non-error status.
Temp traps
Status
Error
Description
Normal
The sensor is working correctly and the temperature is within preset thresholds
No sensor has been detected
NotFound
Reading
TempLow
TempHigh
ReadError
Lost
Temp status currently being read
x
x
x
x
x
Temperature at the sensor below preset low threshold
Temperature at the sensor exceeds preset high threshold
Unable to read Temp status
Sensor initially detected but communication to the sensor has been lost
Communication to the sensor has been lost
NoComm
Humidity Trap
The Humidity trap is generated whenever the umidity on a temperature/humidity sensor is beyond preset
thresholds. Humidity traps include the reported relative humidity, humidity status, Location of the AmpMeter
PDU, and identifier and name of the affected sensor.
Any error state generates a Humidity trap and triggers the trap timer. A new trap is generated at the end of every
timer period until the Humidity returns to a non-error status.
Humidity traps
Status
Error
Description
Normal
The sensor is working correctly and the relative humidity is within preset thresholds
No sensor has been detected
NotFound
Reading
HumidLow
HumidHigh
ReadError
Lost
Humidity status currently being read
x
x
x
x
x
Relative humidity at the sensor below preset low threshold
Relative humidity at the sensor exceeds preset high threshold
Unable to read Humidity status
Sensor initially detected but communication to the sensor has been lost
Communication to the sensor has been lost
NoComm
Page 40 - 301-0399-3 Rev B.
4. Advanced Operations
Configuring Traps
SNMP Trap Command Summary
Command
Description
Set Trap EM Status
Set Trap THS Status
Set Trap THS Temp
Set Trap THS Temphigh
Set Trap THS Templow
Set Trap THS Humid
Set Trap THS Humidhigh
Set Trap Tower Status
Set Trap Infeed Status
Set Trap Infeed Load
Set Trap Infeed HighThresh
Set Trap Outlet Change
Set Trap Outlet Status
Show Traps
Enables or disables the Environmental Monitor Status trap
Enables or disables a temperature/humidity sensor Status trap
Enables or disables a temperature/humidity sensor Temp trap
Sets a temperature/humidity sensor Temp trap high limit
Sets a temperature/humidity sensor Temp trap low limit
Enables or disables a temperature/humidity sensor Humid trap
Sets a temperature/humidity sensor Humid trap high limit
Enables or disables the Tower Status trap
Enables or disables the Infeed Status trap off
Enables or disables the Infeed Load trap
Sets the Infeed Load trap high limit
Enables or disables the Outlet Change trap
Enables or disables the Outlet Status trap
Displays trap configurations
Enabling or Disabling a Status trap
The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed, Outlet,
Environmental Monitor or Sensor.
To Enable or Disable a Status trap:
At the AmpMeter PDU: prompt, type set trap (tower, infeed, outlet, em or ths) status, followed by the
tower, infeed, outlet, Environmental Monitor or sensor name, and on or off. Press Enter, or
Type set trap (tower, infeed, outlet, em or ths) status all, followed by on or off and press Enter.
Examples
The following command enables the Status trap for the first tower, using the tower’s absolute name:
AmpMeter PDU: set trap tower status .a on<Enter>
The following command enables the Status trap for the tower named Florida_HQ_1:
AmpMeter PDU: set trap tower status Florida_HQ_1 on<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling
an Outlet Status trap automatically enables the Infeed and Tower Status traps for that outlet. Conversely, if a
Tower Status trap is disabled, all associated Infeed Status & Load and Outlet Status traps will be disabled.
301-0399-3 Rev B. - Page 41
4. Advanced Operations
Enabling or Disabling a Load trap
The Set Trap Infeed Load command is used to enable or disable an Infeed Load trap.
To Enable or Disable a Load trap:
At the AmpMeter PDU: prompt, type set trap infeed load, followed by the infeed name, and on or off. Press
Enter, or
Type set trap infeed load all, followed by on or off and press Enter.
Examples
The following command enables the Load trap for second infeed on the first tower, using the infeed’s absolute
name:
AmpMeter PDU: set trap infeed load .AB on<Enter>
The following command disables the Load trap for all infeeds:
AmpMeter PDU: set trap infeed load all off<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling
an Infeed Load trap automatically enables the Infeed and Tower Status traps for that infeed.
Setting the Infeed Load limit
The Set Trap Infeed Loadhigh command is used to set the upper load limits for an input feed.
To set the infeed load limit:
At the AmpMeter PDU: prompt, type set trap infeed loadhigh, followed by the infeed name, and a value
from 0 to 255 in amperes. Press Enter.
Example
The following command sets the infeed load limit for the second infeed on the first tower to 25 amperes, using
the infeed’s absolute name:
AmpMeter PDU: set trap infeed loadhigh .ab 25<Enter>
Enabling or Disabling a Change trap
The Set Trap Outlet Change command is used to enable or disable an Outlet Change trap.
To Enable or Disable a Change trap:
At the AmpMeter PDU: prompt, type set trap outlet change, followed by the outlet name and on or off. Press
Enter, or
Type set trap outlet change all, followed by on or off and press Enter.
Example
The following command enables the Change trap for the third outlet on the first infeed of the second tower,
using the outlet’s absolute name:
AmpMeter PDU: set trap outlet change .ba3 on<Enter>
Enabling or Disabling the Temp trap
The Set Trap THS Temp command is used to enable or disable the Temp trap.
To Enable or Disable the Temp trap:
At the AmpMeter PDU: prompt, type set trap ths temp, followed by the sensor name and on or off. Press
Enter.
Example
The following command enables the Temp trap for the first temperature-humidity sensor:
AmpMeter PDU: set trap ths temp .a1 on<Enter>
Page 42 - 301-0399-3 Rev B.
4. Advanced Operations
Setting the Temperature sensor threshold limits
The Set Trap THS Templow and Set Trap THS Temphigh commands are used to set the lower and upper
threshold limits for the Temperature sensor.
To set the Temperature threshold limits:
At the AmpMeter PDU: prompt, type set trap ths, templow or temphigh, followed by the sensor name and
a value from 0 to 127 in degrees Celsius. Press Enter.
Example
The following command sets the second temperature high threshold limit to 95:
AmpMeter PDU: set trap ths temphigh .a2 95<Enter>
Enabling or Disabling the Humid trap
The Set Trap THS Humid command is used to enable or disable the Humid trap.
To Enable or Disable the Humid trap:
At the AmpMeter PDU: prompt, type set trap ths humid, followed by the sensor name and on or off. Press
Enter.
Example
The following command enables the Humid trap for the first temperature-humidity sensor:
AmpMeter PDU: set traps ths humid .a1 on<Enter>
Setting the Humidity sensor threshold limits
The Set Trap THS Humidlow and Set Trap THS Humidhigh commands are used to set the lower and upper
threshold limits for the Humidity sensor.
To set the Humidity threshold limits:
At the AmpMeter PDU: prompt, type set trap ths, humidlow or humidhigh, followed by the sensor name
and a value from 0 to 100 in percent relative humidity. Press Enter.
Example
The following command sets the first humidity sensor low threshold limit to 5:
AmpMeter PDU: set trap ths humidlow .a1 5<Enter>
301-0399-3 Rev B. - Page 43
4. Advanced Operations
Displaying trap configuration information
The Show Traps command displays information about all traps.
To display trap information:
At the AmpMeter PDU: prompt, type show traps and press Enter.
Example
The following command requests trap configuration information:
AmpMeter PDU: show traps <Enter>
Tower trap configuration:
Tower
ID
Tower
Name
Status
Trap
.A
.B
Florida_HQ_1
Florida_HQ_2
ON
ON
More (Y/es N/o): y
Input feed trap configuration:
Input
Feed ID Feed Name
Input
Status
Trap
Load
Trap
High
Thresh
.AA
.BA
HQ_1_Infeed_A
HQ_2_Infeed_A
ON
ON
ON
ON
255 A
255 A
More (Y/es N/o): y
Environmental Monitor .A trap configuration:
Name: Florida_HQ_1
Status Trap: ON
Temperature/Humidity Sensor .A1
Temperature/Humidity Sensor .A2
Name: Temp_Humid_Sensor_A1
Status Trap: ON
Name: T/H2_Florida_HQ_1
Status Trap: ON
Temp Trap: ON
Temp Trap: ON
Low: 0
High: 127 Deg.C
Humid Trap: ON
Low: 5
High: 100 % RH
Deg.C
Low: 0
High: 95 Deg.C
Humid Trap: ON
Low: 0
High: 100 % RH
Deg.C
% RH
% RH
Page 44 - 301-0399-3 Rev B.
5. Appendices
To reset to factory defaults from the HTML interface.............................................................46
To reset to factory defaults from the command line ...............................................................46
To reset to factory defaults using the reset button .................................................................46
To initiate an FTP upload session from the HTML interface.................................................46
To initiate an FTP upload session from the command line ...................................................46
Models...........................................................................................................................................47
Power Ratings..............................................................................................................................47
Physical Specifications ...............................................................................................................48
Data Connections........................................................................................................................49
Branch Circuit Protection............................................................................................................49
301-0399-3 Rev B. - Page 45
5. Appendices
Resetting to Factory Defaults
You may reset the non-volatile RAM that stores all configurable options. This clears all administrator-editable
fields and resets all command line configurable options to their default values, including all user accounts.
You may reset the unit to factory defaults from the command line or the HTML interface, or by pressing the
reset button. You must have administrator-level privileges to issue the command. Using the reset button may
be necessary when a forgotten password prevents administrator login. Each of the methods updates the
current working configuration to the factory defaults.
NOTE: Resetting the unit resets all TCP/IP and Telnet/Web configurations. Reconfiguring the TCP/IP and
Telnet/web settings will be required.
To reset to factory defaults from the HTML interface
On the Restart page in the Tools section of the HTML interface, select Restart and reset to factory
defaults from the drop-down menu and press Apply.
To reset to factory defaults from the command line
At the AmpMeter PDU: prompt, type restart factory and press Enter.
To reset to factory defaults using the reset button
Locate the recessed reset button directly beside the Serial & Ethernet ports. You will need a non-conductive,
non-metallic tool that fits inside the recess.
Insert the tool in the recess, then depress and hold the reset button for at least ten seconds.
NOTE: If the reset button is depressed and held for more than 15 seconds, the reset will abort.
Uploading Firmware
You may upload new versions of firmware using File Transfer Protocol (FTP). This allows access to new
firmware releases for firmware improvements and new features additions.
NOTE: To begin an FTP upload session, you must first configure the FTP Host address, username/password,
filename and filepath. For information on configuring the FTP settings required for firmware upload see FTP
You may initiate an FTP upload session by issuing a command or from the HTML interface. You must have
administrator-level privileges to initiate an upload.
To initiate an FTP upload session from the HTML interface
On the Restart page in the Tools section of the HTML interface, select Restart and upload firmware via
FTP from the drop-down menu and press Apply.
Upon issuing this command the unit will restart and upload the firmware file specified with the FTP Filename
information.
To initiate an FTP upload session from the command line
The Restart FTPLoad command initiates an upload of firmware. Upon issuing this command the unit will restart
and upload the firmware file specified with the FTP Filename command from the previously configured FTP
To initiate an FTP firmware upload session:
At the AmpMeter PDU: prompt, type restart ftpload and press Enter.
Page 46 - 301-0399-3 Rev B.
5. Appendices
Technical Specifications
Models
Europe/Asia
Model
Voltage
Inlet Cordset and Plug (10’)
IEC 60320/C20*
Outlets
12 IEC 60320/C13
12 IEC 60320/C13
12 IEC 60320/C19
24 IEC 60320/C13
48 IEC 60320/C13
84 IEC 60320/C13
RA12-2-C20
RA12-2-30932
230V, 60Hz
230V, 60Hz
IEC 60309, 32A 3-pin 6Hr Blue
IEC 60309, 32A 3-pin 6Hr Blue
IEC 60309, 32A 3-pin 6Hr Blue
IEC 60309, 32A 3-pin 6Hr Blue
IEC 60309, 32A 3-pin 6Hr Blue
RA12-D2-30932M 230V, 60Hz
RA24-2-30932 230V, 60Hz
RA48-D2-30932 230V, 60Hz
RA84-D2-30932M 230V, 60Hz
Americas
Model
Voltage
Inlet Cordset and Plug (10’)
NEMA L5-30P, 30A/120V locking
NEMA L6-30P, 30A/208V locking
IEC 60320/C20*
Outlets
12 NEMA 5-20R
RA12-1-L530
RA12-D2-L630
RA12-2-C20
RA24-2-L630
RA48-D2-L630
100-120V, 50/60Hz
208-240V, 50/60Hz
208-240V, 50/60Hz
208-240V, 50/60Hz
208-240V, 50/60Hz
12 IEC 60320/C19
12 IEC 60320/C13
24 IEC 60320/C13
48 IEC 60320/C13
84 IEC 60320/C13
NEMA L6-30P, 30A/208V locking
NEMA L6-30P, 30A/208V locking
NEMA L6-30P, 30A/208V locking
RA84-D2-L630M 208-240V, 50/60Hz
* Input cordset selected at time of purchase.
Power Ratings
Europe/Asia
O utput C urrent R atings
L’indice du courant de sortie
Input C urrent R atings 1
L’indice du courant d’entrée
Eingangsstromstärke
Ausgangsstromstärke
Vo ltage
Tension
C urrent
Courrant
Strom
Vo ltage
Tension
O utlet
Prise
B ranch C ircuit
Circuit de la Branche
Zweigstromkreis
T o tal
Total
M o del
M odele
P hase 2
M odell
Spannung
Spannung
Anschlussstelle
Insgesamt
230V 50/ 60H z
230V
50/60Hz
230V
50/60Hz
RA12-2-C20
10
10
10
10
10
10
16
16
20
20
20
20
20
16
230V
50/60Hz
230V
50/60Hz
RA12-2-30932
RA12-D2-30932M
RA24-2-30932
RA48-D2-30932
RA64-D2-30932M
32
32
230V
50/60Hz
A: 32
B: 32
230V
50/60Hz
A: 32
B: 32
230V
50/60Hz
230V
50/60Hz
32
32
230V
50/60Hz
A: 32
B: 32
230V
50/60Hz
A: 32
B: 32
230V
50/60Hz
A: 32
B: 32
230V
50/60Hz
A: 32
B: 32
1 All current ratings are in amperes. Tous les indices de courant sont en ampères. Alle Angaben der Stromstärke erfolgen in
Ampere.
2 Each branch circuit or phase consists of: Chaque circuit de la branche comporte: Jeder Zweigstromkreis besteht aus:
12HDx -
2 outlets, prises, Anschlüsse. Input, Entrée, Eingang A, B: 1+2, 3+4, 5+6
12Vx, 24VDx
One 6-outlet module; 6 outlets. 1 série de 6 prises de courants, soit au total 6 prises.
1 gekuppelten Modulen mit je 6 Anschlüssen: 6 Anschlüsse. Input, Entrée, Eingang A, B: 1a, 2a, 3a
24Vx, 48VDx
84VDx
Two 6-outlet module; 12 outlets. 2 série de 6 prises de courants, soit au total 12 prises.
2 gekuppelten Modulen mit je 6 Anschlüssen: 12 Anschlüsse. Input, Entrée, Eingang A, B: 1a+1b,
2a+3b, 3a+3b
Two 7-outlet module; 14 outlets. 2 série de 7 prises de courants, soit au total 14 prises.
2 gekuppelten Modulen mit je 7 Anschlüssen: 14 Anschlüsse. Input, Entrée, Eingang A, B: 1a+1b,
2a+3b, 3a+3b
301-0399-3 Rev B. - Page 47
5. Appendices
Americas
O utput C urrent R atings
L’indice du courant de sortie
Ausgangsstromstärke
Input C urrent R atings 1
L’indice du courant d’entrée
Eingangsstromstärke
Vo ltage
C urrent
Vo ltage
O utlet
B ranch C ircuit
T o tal
M o del
P hase
M odele
Tension
Courrant
Tension
Prise
Circuit de la Branche
Total
M odell
Spannung
Strom
Spannung
Anschlussstelle
Zweigstromkreis
16
Insgesamt
100-120V 50/ 60H z
10 0 - 12 0 V
50/60Hz
10 0 - 12 0 V
50/60Hz
RA12-1-L530
16
24
2 4
208-240 60H z
RA12-D2-L630
208-240V
60Hz
A: 24
B: 24
208-240V
60Hz
A: 24
B: 24
12
12
12
12
12
16
16
16
16
16
208-240V
60Hz
208-240V
60Hz
RA12-2-C20
16
16
208-240V
60Hz
208-240V
60Hz
RA24-2-L630
RA48-D2-L630
RA84-D2-L630M
24
2 4
208-240V
60Hz
A: 24
B: 24
208-240V
60Hz
A: 24
B: 24
208-240V
60Hz
A: 24
B: 24
208-240V
60Hz
A: 24
B: 24
1 All current ratings are in amperes. Tous les indices de courant sont en ampères. Alle Angaben der Stromstärke erfolgen in
Ampere.
2 Each branch circuit or phase consists of: Chaque circuit de la branche comporte: Jeder Zweigstromkreis besteht aus:
12HDx -
2 outlets, prises, Anschlüsse. Input, Entrée, Eingang A, B: 1+2, 3+4, 5+6
12Vx, 24VDx
One 6-outlet module; 6 outlets. 1 série de 6 prises de courants, soit au total 6 prises.
1 gekuppelten Modulen mit je 6 Anschlüssen: 6 Anschlüsse. Input, Entrée, Eingang A, B: 1a, 2a, 3a
24Vx, 48VDx
84VDx
Two 6-outlet module; 12 outlets. 2 série de 6 prises de courants, soit au total 12 prises.
2 gekuppelten Modulen mit je 6 Anschlüssen: 12 Anschlüsse. Input, Entrée, Eingang A, B: 1a+1b,
2a+3b, 3a+3b
Two 7-outlet module; 14 outlets. 2 série de 7 prises de courants, soit au total 14 prises.
2 gekuppelten Modulen mit je 7 Anschlüssen: 14 Anschlüsse. Input, Entrée, Eingang A, B: 1a+1b,
2a+3b, 3a+3b
Physical Specifications
Operating
32° to 122° F (0° to 50° C)
Elevation(above MSL) 0 to 10,000 ft (0 to 3000m)
Storage
Temperature
-40° to 185° F (-40° to 85° C)
0 to 50,000 ft (0 to 15000m)
10 to 90%, non-condensing
Relative Humidity
10 to 90%, non-condensing
Dimensions (H x W x D)
Weight
RA12-1
31.25 x 1.75 x 2.25
31.25 x 1.75 x 2.25
3.5 x 17.0 x 10.0 in.
63.5 x 1.75 x 2.25 in.
63.5 x 3.5 x 2.25 in.
66.0 x 3.5 x 2.25 in.
(794 x 45 x 57 mm)
7.4 lbs
7.4 lbs
17 lbs
10 lbs
(16 kg)
(16 kg)
(37 kg)
(22 kg)
RA12-2
(794 x 45 x 57 mm)
(89 x 437 x 178 mm)
(1617 x 45 x 57 mm)
(1617 x 89 x 57 mm)
(1678 x 89 x 57 mm)
RA12-D2
RA24-2
RA48-D2
RA84-D2
17.4 lbs (38 kg)
24 lbs (53 kg)
Page 48 - 301-0399-3 Rev B.
5. Appendices
Data Connections
RS-232 port
The AmpMeter PDU may be equipped standard with an RJ45 DTE RS-232c serial port. This connector may be
used for direct local access or from other serial devices such as a terminal server. An RJ45 crossover cable is
provided for connection to an RJ45 DCE serial port.
Pin
1
DTE Signal Name
Input/Output
Output
Request to Send
RTS
2
Data Terminal Ready DTR
Output
3
Transmit Data
Signal Ground
Signal Ground
Receive Data
Data Set Ready
Clear to Send
TD
Output
4
5
87654321
6
RD
Input
Input
Input
7
DSR
CTS
8
RJ45 to DB9F serial port adapter
An RJ45 to DB9F serial port adapter may be provided for use in conjunction with the RJ45 crossover cable to
connect to a PC DB9M DCE serial port. The adapter pinouts below reflect use of the adapter with the provided
RJ45 crossover cable.
Pin
1
DCE Signal Name
Input/Output
2
Receive Data
Transmit Data
RD
TD
Output
Input
3
5
4
3
2
1
9
8
7
6
4
Data Terminal Ready DTR
Signal Ground
Input
5
6
Data Set Ready
Request to Send
Clear to Send
DSR
RTS
CTS
Output
Input
7
8
Output
Branch Circuit Protection
Always disconnect the power supply cord before opening to avoid electrical shock.
Afin d’éviter les chocs électriques, débranchez le cable électrique avant d’ouvrir.
Immer Netzleitung auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden.
Cabinet Distribution Units feature Branch Circuit protection on all outlets in the form of internal fuses. These
fuses meet the strict safety requirements of UL/CSA 60950-1 for Branch Circuit Protection.
Time-Delay Fuses – Class G
Amperes
Bussman Part Number
20
SC-20
CooperBussman product data-sheet #1024
301-0399-3 Rev B. - Page 49
|