LST Smoke Alarm LAB48 User Manual

LED Display Field  
LAB48  
• 48 freely programmable LED pairs  
• Indication of events and conditions of  
fire detection control panels Series  
BC216 or BC016  
• Installation in control panels  
Series BC216 or  
LED Display Tableau LAT288  
• Different LED colors available  
• Individual labeling by means of  
inserted text labeling strips  
Description  
The LED Display Field LAB48 serves for the indication 48 LED pairs are arranged in two rows on the com-  
of the events of detectors, detector zones, actuations, ponentry. Each LED pair can be freely assigned to the  
transmitting devices, or alarming devices on fire detec- individual events. The left LEDs are intended for dis-  
tion control panels Series BC216 or BC016 as well as playing the alarm or the activation, or for displaying a  
the events of flooding zones or extinguishing systems system condition, respectively. The right LEDs indicate  
on extinguishing control panels Series LC216.  
the disablement or the fault condition of the assigned  
system component.  
The LED Display Field is designed to be installed into The LED Display Field is available in multiple versions  
fire detection control panels Series BC216 or into the with different LED colors for varying applications.  
LED Display Tableau LAT288:  
• The LAB48 can be mounted into a fire detection con- Each LED pair can be individually labeled by means of  
trol panel Series BC216 with display and operating labeling strips which are inserted into the front foil of  
field, to which it is directly connected.  
• The LED Display Tableau LAT288 can accommodate  
the case cover.  
up to 3 LED Display Fields LAB48 and the Remote The componentry is shipped with the necessary ac-  
Tableau Drive Unit PTU288-1. Due to the actuation via cessory for trouble-free mounting on the case cover of  
the INFO bus, the LED Display Tableau is a universal the fire detection control panel or in the LED Display  
remote tableau for all fire detection control panels Se- Tableau.  
ries BC216 and BC016 as well as the extinguishing  
control panel Series LC216.  
Specifications  
Current consumption at 24V  
Ambient temperature  
Dimensions L × W × H  
Weight  
typ. 2mA no active LED, +0.25mA per LED  
-20°C to +60°C  
176 × 120 × 15 (mm)  
60g  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
LAB48_DBL_LST_EN_0804.PDF • PAGE 1  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
 

La Crosse Technology Weather Radio WS 2510 User Manual
Lenoxx Electronics Air Cleaner PMAC 12C User Manual
Lenoxx Electronics Conference Phone PH 550 User Manual
Lexmark Network Card x560 User Manual
Lightolier Work Light C6E17OVW User Manual
Logitech Universal Remote 880 User Manual
Lucent Technologies Network Card MRT 36H User Manual
Maytag Gas Heater LMDV 33 SERIES User Manual
Maytag Washer Dryer MAF9601 User Manual
McIntosh Stereo Amplifier C2200 User Manual